The Woodward 8915-887 is a microprocessor-based digital control device primarily used to display and control turbine operating status and parameters. It controls turbine start, stop, acceleration, and deceleration by operating single or dual split-range actuators to drive steam inlet valves, thereby achieving speed control of turbocompressors. It serves industrial steam turbines, steam turbines, utility turbo-generators, and turboexpanders.

Detailed content

Technical Specifications
  • Power Supply: 18–32 VDC (supports 24 VDC input)
  • Display: Two-line × 24-character LED display
  • Enclosure: NEMA 4X or IEC 60529 IP56 rated
  • Inputs: 6 programmable current inputs, 16 discrete contact inputs
  • Outputs: 2 actuator outputs, 8 relay outputs, 6 programmable current outputs
  • Communication Interfaces: RS-232, RS-422, RS-485
  • Software: OpView™ and 505View
  • Operating Temperature: –20 to +60 °C
  • Storage Temperature: –40 to +85 °C
  • Weight: Approx. 9.11 lbs (4.13 kg)
Functional Features
  • Menu-driven software for intuitive on-site configuration
  • Triple independent overspeed protection logic with overspeed test button
  • Emergency stop function for immediate shutdown
  • Automatic control mode switching upon sensor failure
  • Local/remote control priority selection
  • PID closed-loop control capability
  • High flexibility and scalability for specific application configuration
Application Scenarios
  • Industrial steam turbines, steam turbines, utility turbo-generators, turboexpanders
  • Oil & gas, petrochemical, chemical, metallurgy, paper printing, energy, power transmission and distribution, water treatment, municipal boiler heating
Installation Requirements
  • Modular structure form, control room installation
  • Proper ventilation to maintain 0–60 °C ambient temperature
  • Keep relative humidity ≤ 60% (non-condensing)
Usage Notes
  • Verify voltage is within 18–32 VDC before powering on
  • Do not exceed specified temperature and humidity limits
  • Perform regular inspection of I/O connections and communication ports