Product Name: Real Power Sensor (4–20 mA Output)

Product Introduction: A three-phase real power transducer designed for accurate measurement of active power (kW) in industrial AC circuits. It converts voltage and current inputs into a linear 4–20 mA DC output signal representing real power flow. This model supports unidirectional power measurement (import or export) and is widely used in generator load sharing and power monitoring systems.

Detailed content

Technical Specifications:
  • Power Supply: 24 VDC (18–32 VDC)
  • Input: 3-phase 120/480 VAC voltage; 5 A CT current
  • Output: 4–20 mA DC (isolated, proportional to kW)
  • Accuracy: ±0.2% full scale
  • Frequency Range: 45–65 Hz
  • Response Time: ≤150 ms
  • Operating Temperature: -40 °C to +85 °C
  • Functional Features:
  • True-RMS real power calculation for balanced/unbalanced loads
  • Isolated 4–20 mA output for long-distance signal transmission
  • Adjustable measurement range via internal jumpers
  • Built-in surge protection for industrial environments
  • Compact DIN-rail mount enclosure
  • Compatibility with Woodward DSLC and load sharing controllers

    Application Scenarios:

  • Generator set load sharing control systems
  • Industrial plant power consumption monitoring
  • Marine vessel electrical power management
  • Micro-grid renewable energy power flow measurement
  • Utility interconnection and demand response systems