Digital guide

You are here:

Woodward 8272-287

Product Name: Real Power Sensor for Load Sharing Systems

Product Introduction: A high-precision three-phase power sensing module engineered for generator load sharing and power monitoring applications. It accurately measures real power (kW) in three-phase AC circuits and outputs a standardized 4–20 mA signal proportional to power flow, supporting both imported and exported power measurement. Integrated load bridge and load-sharing line terminals enable direct integration into isochronous parallel control systems.

Detailed content

Technical Specifications:
  • Power Supply: 24 VDC (18–32 VDC range)
  • Input: 3-phase voltage (120/480 VAC) and current (5 A CT secondary)
  • Output: 4–20 mA DC (isolated, proportional to real power)
  • Measurement Range: Adjustable via internal DIP switches
  • Accuracy: ±0.2% full scale
  • Response Time: ≤100 ms
  • Operating Temperature: -40 °C to +70 °C
  • Mounting: DIN rail or panel mount

    Functional Features:

  • Precise true-RMS real power calculation for balanced/unbalanced loads
  • Galvanic isolation between input, output, and power supply
  • Configurable power direction (import/export) via wiring
  • Built-in load sharing network interface for multi-generator parallel systems
  • Low temperature drift and high noise immunity for industrial environments
  • Compact, rugged enclosure for cabinet installation

    Application Scenarios:

  • Multi-generator isochronous parallel power stations
  • Marine integrated power distribution systems
  • Island and micro-grid independent power systems
  • Industrial plant power monitoring and load management
  • Utility interconnection power flow measurement