Digital guide

You are here:

Schneider Electric AS-P830-000

Product Name​
Modicon 800-series 24 VDC PLC power supply module.
Overview​
Regulated AC-to-DC power module for Modicon 800-series PLC racks. It supplies 24 VDC to the backplane, processor modules, I/O modules and related control electronics.

Detailed content

Technical Specifications​
  • Series: Modicon 800-series legacy PLC
  • Input voltage: 115/230 VAC selectable by jumper or switch
  • Input frequency: 47–63 Hz
  • Output voltage: 24 VDC regulated
  • Output current: high-capacity backplane rating; exact ampere/Watt value depends on revision
  • Isolation: HV isolation between AC input and DC output
  • Protection: current limiting, overvoltage protection
  • Cooling: passive heatsink/convection design
  • Indicator: power OK LED
  • Mounting: 800-series power slot/rack
Functional Features​
Stable backplane voltage under loaded I/O configurations, overload and overvoltage protection, EMI/RFI filtering, diagnostic LED, no internal fan in described legacy design.
Application Scenarios​
Automotive assembly PLC power, steel-mill rolling control cabinets, water-treatment pump control, chemical batch systems, general 800-series controller backplane supply.
Material Composition​
Sheet-metal/heatsink enclosure components, industrial-grade capacitors, transformers/regulator circuitry, PCB, AC terminal block.
Structural Characteristics​
Plug-in PLC power module, dedicated power-supply slot form factor, front LED, AC terminals, backplane DC distribution contacts.
Working Principle​
AC input passes through filtering and isolation, then regulation circuitry converts it to regulated 24 VDC. The output distributes power across the rack backplane to processor and I/O cards while protection circuits limit overcurrent and clamp overvoltage faults.
Installation Requirements​
Set 115/230 VAC selector before energizing. Install in the specified power slot. Use properly sized AC conductors and ground the chassis. Verify backplane load against module output rating. Allow ventilation space around heatsink surfaces.
Usage Precautions​
Never change AC voltage selection under power. Inspect electrolytic capacitors in long-service units. If power LED fails, check AC input, fuse and backplane short circuits before module replacement. Use only in compatible 800-series racks.