Digital guide

You are here:

SCHNEIDER ELECTRIC 60325-01D

Product Name:​ Multi9 C60 UL489 Miniature Circuit Breaker, 1-pole, 7 A, D curve
Product Introduction:​ This device provides branch-circuit overcurrent protection for industrial control panels, commercial distribution and equipment disconnect applications. The D trip characteristic is intended for circuits with high inrush current.
Technical Specifications:​ Rated current 7 A, single-pole, rated voltage 120 V AC per Schneider 60325 listing, breaking capacity 10 kA, trip curve D, terminal type tunnel/ring, standard UL489.

Detailed content

Trip Characteristic:​ D curve instantaneous release 10–14 times rated current.
Materials And Structure:​ Molded thermoset/thermoplastic housing, copper current path, magnetic solenoid and thermal bimetal elements, tunnel and ring terminal connections.
Working Principle:​ The thermal element responds to sustained overload by bending the bimetal and opening the contacts; the magnetic element releases instantly under short-circuit current exceeding the D-curve threshold.
Installation Requirements:​ Mount on a compatible DIN rail or panel arrangement per UL489 enclosure design, torque terminals to Schneider specification, provide correctly sized line-side conductors and upstream fusing/breaker coordination, install with adequate clearance for heat dissipation.
Usage Notes:​ Confirm the suffix 01D against the Schneider product label and local voltage/system requirements before replacement. Do not use in DC applications unless the model rating explicitly permits DC. Test manually using the approved actuator after installation and after any fault event.