Honeywell CC-TAIM01
Product Name: Low-Level Analog Input IOTA (LLMUX Termination Assembly)
Product Overview: The CC-TAIM01 (part number 51305959-175) is a low-level analog input termination assembly (IOTA/baseplate) from Honeywell’s Experion PKS C300 Series I/O family. It serves as the physical termination interface for the CC-PAIM01 low-level analog input multiplexer (MUX) module, providing high-density field wiring for thermocouple (TC) and RTD temperature signals. It is a passive backplane that requires the active CC-PAIM01 module for full functionality.
Detailed content
Key Technical Specifications:
- Model: CC-TAIM01
- Part Number: 51305959-175
- Type: Low-Level Analog Input IOTA / Baseplate (Non-redundant PMIO LLMUX architecture)
- Compatible Module: CC-PAIM01
- Input Channels: 64 (in 16-channel increments)
- Input Types: Thermocouple (TC), RTD, millivolt (mV)
- Nominal TC Range: -20 to +100 mV
- Gain Error (TC range): 0.050% full scale max (when paired with CC-PAIM01)
- CMRR (50/60 Hz): 120 dB min (1000Ω source max)
- NMRR at 50/60 Hz: 60 dB min
- Scan Rate: 1 second fixed (up to 64 channels/sec)
- CMV Rating: ±250 VDC or VAC RMS
- Isolation: Channel-to-channel, channel-to-PM, channel-to-power supply
- Open Thermocouple Detection (OTD): Guaranteed no-trip at ≤1000Ω, guaranteed trip at ≥1500Ω
- Surge Protection: EN 61000-4-5 (1 kV line-line, 2 kV line-ground)
- Mounting: Series C I/O rack / Carrier
- Power Consumption: 5W (typical)
- Operating Temperature: 0°C to +60°C
- Storage Temperature: -40°C to +85°C
- Protection Rating: IP20 (rack mounted)
- Certifications: CE, UL, CSA
- Construction: Rugged Printed Wire Assembly (PWA)
Functional Features:
- Complete isolation eliminating ground loops and cross-channel interference
- High precision temperature measurement (±0.05% full-scale gain error)
- Hot-swappable module replacement
- Supports open thermocouple detection
Working Principle: The CC-TAIM01 is a passive baseplate providing mechanical and electrical termination for field thermocouple/RTD wiring. The active CC-PAIM01 module plugs into this baseplate, performing signal conditioning, multiplexing, and A/D conversion. Millivolt-level signals from TCs are routed through the IOTA to the MUX module with full galvanic isolation.
Application Scenarios: Dense temperature monitoring in process plants; PMIO (Process Manager I/O) systems within Experion PKS C300 architecture; suitable for control room environments with strong EMI immunity requirements.
Installation & Usage Notes:
- Install in a standard Series C I/O rack.
- The CC-TAIM01 MUST be paired with a CC-PAIM01 module – it is non-functional alone.
- Ensure proper cold junction compensation reference if required by the application.
- Maintain surge protection grounding per EN 61000-4-5.
- Verify channel-to-channel isolation before energizing.