Product Name: GE THJK Series 250A Thermal-Magnetic Molded Case Circuit Breaker
Product Overview: The THJK436F000-250A is an industrial-grade thermal-magnetic molded case circuit breaker (MCCB) produced by GE with a rated current of 250A. It is used for circuit protection in low-voltage power distribution systems, providing both overload and short-circuit protection functions. It is suitable for motor circuits, feeder circuits, and main distribution circuits.

Detailed content

Technical Specifications:
  • Brand: GE
  • Model: THJK436F000-250A
  • Series: THJK Series
  • Rated Current: 250 A
  • Poles: 3-Pole (3P)
  • Rated Insulation Voltage: 690 V AC
  • Rated Operating Voltage: 600 V AC
  • Rated Short-Circuit Breaking Capacity (Icu): 65 kA @ 480 V AC
  • Rated Service Short-Circuit Breaking Capacity (Ics): 50 kA @ 480 V AC
  • Trip Unit Type: Thermal-Magnetic
  • Overload Trip Setting Range: 160 A ~ 250 A (adjustable)
  • Short-Circuit Trip Setting: Fixed, approximately 10×In (2500 A)
  • Frame Size: N-Frame (compact molded case circuit breaker)
  • Power Consumption: < 15 W at full load
  • Mechanical Life: 20,000 operations
  • Electrical Life: 10,000 operations at rated load
Functional Features:
  • Thermal-magnetic dual trip protection: Thermal trip provides long-delay overload protection, magnetic trip provides instantaneous short-circuit protection
  • Overload trip current is field-adjustable to adapt to different load requirements
  • Equipped with electric operator interface supporting remote opening/closing
  • Front panel clearly displays open/close status and trip cause indication
Structural Features:
  • Housing Material: Flame-retardant thermoplastic material (UL94 V-0)
  • Front Panel: Open/close handle, trip indicator window, overload setting knob
  • Terminals: Top and bottom wiring, bolt connection, maximum conductor size 3/0 AWG (85 mm²)
  • Installation: Vertical mounting, supports DIN rail or screw fixing
Working Principle:
  • During normal operation, current passes through the thermal trip bimetallic strip and magnetic trip coil
  • During overload, the bimetallic strip bends from heating and triggers the trip mechanism to disconnect the circuit
  • During short circuit, the magnetic trip coil generates strong magnetic force, instantly pushing the trip mechanism to disconnect the circuit
Installation Requirements:
  • Install vertically inside the distribution cabinet with consistent top-bottom wiring direction
  • Connect the power supply side to the input terminal and load side to the output terminal
  • The grounding terminal must be reliably connected to protective earth
  • Sufficient heat dissipation space must be maintained around, with vertical spacing not less than 50 mm
  • Operating environment temperature: -25°C to +70°C
  • Altitude not exceeding 2000 m (derating required above this)
Usage Notes:
  • Regularly check the tightness of terminal connections to prevent excessive contact resistance
  • The trip setting must never exceed the rated current of 250 A
  • After short-circuit breaking, the contact condition must be checked before reclosing
  • Applicable Industries: Power plant auxiliary power systems, industrial distribution, building distribution, petrochemical plant distribution, data center distribution