Product Name:​ GE THED Series 3-Pole Molded Case Circuit Breaker (MCCB)
Overview:​ The THED136125 is a high interrupting capacity, bolt-on molded case circuit breaker from GE’s E150 line. It provides overcurrent and short-circuit protection for three-phase commercial and industrial power distribution systems and serves as a direct replacement for legacy TED136125 units.

Detailed content

Technical Specifications:
  • Frame Type:​ E150, THED series
  • Poles:​ 3
  • Rated Current:​ 125 A
  • Voltage Rating:​ 240 / 480 / 600 VAC, 250 / 500 VDC
  • Interrupting Capacity (AIC):
    • 65 kA @ 240 VAC
    • 25 kA @ 480 VAC
    • 18 kA @ 600 VAC
    • 10 kA @ 250 VDC
    • 10 kA @ 500 VDC
  • Trip Type:​ Fixed thermal-magnetic, LI (long-time + instantaneous) functions
  • Mounting:​ Bolt-on, feed-through
  • Terminals:​ Line and load lug terminals, Cu/Al rated
  • Wire Range:​ 3 AWG – 3/0 AWG (Copper), 1 AWG – 3/0 AWG (Aluminum)
  • Temperature Rating:​ 40 °C
  • Standards:​ UL 489, CSA C22.2 No.5, NEMA AB-1, HACR rated, reverse feed capable
  • Dimensions:​ 4-1/8 in (W) × 3-3/8 in (D) × 6-5/16 in (H)
  • Options:​ Shunt trip, auxiliary switch, undervoltage release, alarm switch, padlock attachment
Structural Features:​ Molded case housing with quick-make/quick-break, trip-free mechanism; non-interchangeable trip unit; high interrupting capacity construction; bolt-on frame with lug terminals for secure panellboard mounting.
Functional Features:​ Thermal-magnetic trip delivers long-time overload protection and instantaneous short-circuit protection; HACR rated for heating, air-conditioning and refrigeration circuits; reverse feed capable; trip-free design prevents manual hold-closed during fault.
Application Scenarios:​ GE A-Series and Spectra Series panelboards; motor control centers; 600 VAC three-phase commercial and industrial power distribution; HVAC and refrigeration disconnect protection.
Working Principle:​ Under sustained overload the bimetallic thermal element heats and bends, tripping the mechanism after a time inversely proportional to the current magnitude (long-time characteristic). Under a short-circuit the electromagnetic coil generates a instantaneous magnetic force that releases the latch immediately (instantaneous characteristic). Both actions open the contacts and isolate the faulted circuit.
Installation Requirements:​ Mount as a bolt-on breaker in a compatible GE panelboard or MCC; torque the line and load lugs to the specified value for the conductor size; verify the supply phase sequence; install optional accessories (shunt trip, auxiliary contacts) per the relevant GE wiring diagram.
Usage Precautions:​ De-energize and lock out the panel before installation or removal; verify the breaker’s AIC rating meets the available fault current at the installation point; do not exceed 40 °C ambient unless the ampacity is derated; confirm polarity for reverse-feed applications.