Product Name:​ 3-Pole 3-Wire Fusible General-Duty Safety Switch, Type TG, Spec-Setter™ Series
Product Introduction:​ The TG3325R is a GE Industrial Spec-Setter™ Type TG 3-pole, 3-wire general-duty safety switch rated at 400 A and 240 V at 50/60 Hz. It is a fusible switch with a lockable cover and handle, intended for commercial and industrial applications where safety, high performance, and continuity of service are essential.

Detailed content

Technical Specifications:
  • Current rating: 400 A
  • Voltage rating: 240 V, 50/60 Hz
  • Poles / wires: 3 poles / 3 wires
  • Fusible: Yes, uses Class R cartridge fuses
  • Power rating: 50 hp at 240 V AC (standard); 100 hp at 240 V AC (time delay)
  • NEMA rating: NEMA 3R (outdoor enclosure)
  • Conductor size: (1) 2 AWG – 600 KCMIL or (2) 1/0 AWG – 250 KCMIL
  • Dimensions: 49.2 in H × 21.6 in W × 8.9 in D
  • Construction: Steel enclosure
  • Standards: UL 98 Listed, CSA C22.2 No. 4-04 Certified, NEMA KS1, Seismic Certified, WS-865C Federal Specification, GSA Compliant
  • Status: Discontinued product
Functional Features:
  • Fusible design providing short-circuit and overload protection via Class R cartridge fuses
  • Lockable cover and handle preventing unauthorized entry and use
  • NEMA 3R outdoor-rated enclosure
  • Surface-mountable
  • Suitable for use as service equipment
Material Composition:​ Steel enclosure with powder-coat finish; Class R cartridge fuse holders; copper alloy electrical contacts; integral cover interlock (on 30-200 A versions).
Structural Characteristics:
  • Enclosure dimensions: 49.2 in H × 21.6 in W × 8.9 in D
  • Surface-mounted, NEMA 3R enclosure
  • 3-pole, 3-wire fusible switch
  • Lockable handle and cover
Working Principle:​ As a general-duty safety switch, the TG3325R provides a visible disconnect means for 240 V, 3-phase circuits up to 400 A. In the event of an overcurrent or short circuit, the Class R cartridge fuses open to protect the downstream installation. The lockable handle and cover ensure that the switch cannot be inadvertently operated or accessed by unauthorized personnel.
Installation Requirements:​ Surface-mount the steel enclosure. Wire with (1) 2 AWG – 600 KCMIL or (2) 1/0 AWG – 250 KCMIL conductors. Install appropriate Class R cartridge fuses sized for the load and short-circuit capacity. Ensure the enclosure is properly grounded. Mounting must comply with NEC and local electrical codes. The integral cover interlock (for 30-200 A disconnects) provides added protection.
Usage Precautions:​ This product is discontinued—spare parts and replacements may be limited. Only qualified electricians should install or service. Always de-energize the upstream source and verify zero voltage before opening the cover or replacing fuses. Use only Class R cartridge fuses of the correct ampere rating. The NEMA 3R enclosure is suitable for outdoor use, but the lockable cover must remain secured against unauthorized entry.