GE TED134150WL
Product Name: GE TED134150WL 3-Pole Molded Case Circuit Breaker (E150 frame, thermal-magnetic)
Product Overview: The TED134150WL is a member of GE’s E150 product line of thermal-magnetic molded case circuit breakers and switches, rated up to 150 A and 600 V AC. The “WL” suffix indicates the device ships with copper/aluminum line and load lugs. It is intended for branch-circuit protection in load centers and industrial power distribution.
Detailed content
Technical Specifications:
- Frame Type: E150
- Poles: 3
- Continuous Current Rating: 150 A
- System Voltage: 120 V AC, 120/240 V AC, 240 V AC, 277 V AC, 480 V AC, 600 V AC, 125 V DC, 250 V DC, 500 V DC
- Interrupting Ratings: 18 kAIC @ 120/240/277/480 V AC; 14 kAIC @ 600 V AC; 10 kAIC @ 125/250 V DC; 10 kAIC @ 500 V DC
- Trip Style: Non-interchangeable, fixed LI (long-time and instantaneous)
- Trip Function: L (Long-Time), I (Instantaneous)
- Suitable for Reverse Feed: Yes
- Lugs: TC041, TCAL15 (Cu/Al line and load lugs)
- Standard: HACR rated
- Certifications: UL File #E11592, CSA File #LR57114
Functional Features:
- Thermal-magnetic trip unit for reliable overload and short-circuit protection
- Fixed long-time and instantaneous trip characteristics
- Designed for use in GE load centers and panelboards
- All TEB, TED, THED breakers are suitable for reverse feed applications
Performance Parameters:
- Continuous current rating: 150 A
- Operating temperature range consistent with UL/IEEE standards for molded case breakers
- 60/75°C rating through 100 A; 75°C rating above 100 A
Material & Structural Characteristics:
- Construction: Thermoplastic molded case housing
- Conductors/Lugs: Copper-aluminum (Cu/Al) compatible line and load lugs
- Compact 3-pole form factor for panelboard mounting
Installation Requirements:
- Install in compatible GE load centers or panelboards rated for E150 frame
- Torque lugs to manufacturer-specified values (TC041, TCAL15)
- Ensure proper wire sizing per 60/75°C or 75°C rating depending on amperage
- Verify suitability for reverse feed where applicable
Usage Notes:
- Not for switching duty beyond specified ratings
- Non-interchangeable trip—do not attempt to replace trip unit
- De-energize the panel before installation or maintenance