GE TC4040SSE1C

Product Name:​ GE Spectra Series Insulated-Case Circuit Breaker (ICCB)
Introduction:​ Draw-out main breaker for low-voltage switchgear, protecting large 600 V distribution feeders.
Technical Specifications:
  • 4000 A frame, 600 VAC

Detailed content

  • MicroVersaTrip PM electronic trip
  • Interrupting rating: 100 kA @ 480 V
  • LSIG protection (Long, Short, Instantaneous, Ground)
    Features:​ Draw-out carriage, racking test/run positions, communications via trip unit, adjustable thresholds.
    Materials & Structure:​ Glass-reinforced thermoset casing, silver-tungsten contacts, stored-energy spring mechanism, insulated bus stabs.
    Working Principle:​ Trip unit measures current via CTs; on fault exceeds setting, releases latch, spring opens contacts, arc quenched in chambers.
    Installation:​ Bolt to switchgear bus, align draw-out rails, torque primary connections, calibrate trip unit with GE software.
    Precautions:​ Only rack in/out with door interlock satisfied; annual IR scan; never bypass trip unit; test mechanism every 3 years.