Detailed content
Technical Specifications:
-
Output: 0–500 V DC adjustable, 1000–6000 A DC (model-dependent)
-
Power Device: GTO thyristor stack
-
Control Input: 4–20 mA DC
-
Method: Phase-angle firing
-
Response: < 10 ms
-
Cooling: Forced fan, bottom-to-top airflow
-
Protection: Overcurrent, overvoltage, overtemperature, commutation fail, DC short
-
Enclosure: IP20 steel cabinet
Functional Features: Constant-V / constant-I / constant-Q / constant-PF modes, soft-start, hot-swappable drawers.
Working Principle: AVR error signal → firing board → GTO gate pulses → DC output follows command linearly.
Materials: Aluminum extrusion heatsink, silver-plated copper busbars, GTO modules, FR-4 driver PCB.
Installation: Mount in excitation cubicle; maintain 150 mm top/bottom clearance; use copper busbar for DC output; separate signal wire (twisted shielded) from power bus.
Precautions: Never de-energize DC side under load; replace GTO per accumulated conduction hours; inspect fan/filter quarterly.