Digital guide

You are here:

GE SKPA36AT1200

Product Name:​ GE Spectra RMS SKPA36AT1200 — 1200 A, 600 V, 3-Pole Bolt-On Molded Case Circuit Breaker
Overview:​ The SKPA36AT1200 is a high-capacity 3-pole molded case circuit breaker from GE’s Spectra Series SK frame, rated for 1200 A at 600 VAC. It features a Spectra RMS digital solid-state trip system with an electronic LSI (Long-Time, Short-Time, Instantaneous) interchangeable trip unit, providing adjustable and precise circuit protection for demanding industrial power distribution.

Detailed content

Technical Specifications:
  • Manufacturer:​ General Electric
  • Series / Frame:​ Spectra Series, SK Frame
  • Type:​ SKPA
  • Amperage:​ 1200 A
  • Voltage:​ 600 VAC (3-phase)
  • Poles:​ 3
  • Trip System:​ Spectra RMS digital solid-state, electronic LSI interchangeable trip unit
  • Protection Functions:​ LSI — Long-Time, Short-Time, and Instantaneous
  • Interrupting Rating:​ 100 kA @ 480 V (some sources cite 65 kA @ 480 V); 200 kA @ 240 V; 42 kA @ 600 V (UL)
  • Mounting Type:​ Bolt-On / Front Mount
  • Connection:​ Bolt-On (lugs not included)
  • Rating Plug:​ Required for ampere rating configuration (e.g., SRPK1200A1200)
  • Certifications:​ UL Listed, CSA Certified
  • Dimensions (H × W × L):​ 15.51″ × 8.25″ × 7.09″
  • Reverse Fed Applications:​ Suitable
Key Features:
  • Digital RMS sensing trip system for accurate, adjustable protection
  • Interchangeable trip unit allows flexible configuration
  • Very high interrupting capacity for severe fault conditions
  • Current limiting design
  • Bolt-on connection for secure, reliable mounting
  • Solid-state electronic trip for stable performance across temperature variations
Working Principle:​ The Spectra RMS solid-state trip system continuously senses the RMS value of the current. The LSI logic provides long-time overload protection, short-time delay for selective coordination, and instantaneous tripping for high-magnitude faults. When the sensed current exceeds the configured threshold, the trip unit sends a signal to open the contacts, interrupting the fault current.
Application Scenarios:​ Industrial power distribution panels, main incoming breakers for large commercial and industrial facilities, feeder protection in 600 V 3-phase systems, and any application requiring 1200 A of bolt-on circuit protection.
Installation Requirements:
  • Requires a rating plug (e.g., SRPK1200A1200) to set the ampere rating
  • Bolt-on front mounting into compatible Spectra Series enclosures
  • Lugs must be separately procured and installed (not included)
  • Install in accordance with UL/NEC requirements for 1200 A services