Digital guide

You are here:

GE SKLA36AT0800

  • Product Description: Three-pole, 600 V class industrial MCCB frame from GE Spectra RMS series. Requires separate MicroVersaTrip or RMS digital trip unit and rating plug to become functional breaker.
  • Technical Specifications:
    • Frame: SK 1200

Detailed content

    • Poles: 3
    • Continuous rating: 800 A at 600 V AC max
    • Voltage range: 120–600 V AC
    • Interrupting rating: 42 kA @ 600 V, 65 kA @ 480 V, 100 kA @ 240 V
    • Trip type: Electronic solid-state RMS sensing (LSI or LSIG with plug)
    • Dimensions: 15.5 × 8.25 × 5.5 in (H×W×D)
    • Terminals: Copper/aluminum line and load lugs
    • Reverse feed: Supported
    • Certifications: UL 489, CSA
  • Functional Features: Interchangeable trip units, field-adjustable rating plugs, tracking short-time delay, current limiting.
  • Application Scenarios: Main incoming breakers, motor-control-center feeders, generator tie breakers, industrial switchboards.
  • Installation Requirements: Use TK8SPK or equivalent 800 A mounting kit for AV1/AV2/CCB panels, torque lug connections to GE spec, allow vertical clearance for arc venting.
  • Usage Notes: Frame-only unit will not trip without trip module; do not exceed 800 A sensor rating; periodic IR scan recommended in high-load service.

You may also like