GE SGLA36AT0600
Product Name: GE Spectra RMS™ Electronic Trip Molded-Case Circuit Breaker (SG600 Frame)
Introduction: A digitally controlled, solid-state RMS-sensing molded-case circuit breaker from GE’s Spectra RMS series. The electronic trip unit uses digital sampling to determine the true RMS value of sinusoidal and non-sinusoidal load currents, providing precise, adjustable protection. A field-installable, front-mounted rating plug establishes or changes the breaker’s ampere rating.
Detailed content
Technical Specifications:
-
Frame Type: SG600
-
Poles: 3
-
System Voltage: Up to 600 V AC (120 V, 120/240 V, 240 V, 277 V, 480 V, 600 V)
-
Ampere Ratings (via rating plug): 250 A, 300 A, 350 A, 400 A, 450 A, 500 A, 600 A
-
Interrupting Ratings:
-
100 kA IC at 120 V AC, 120/240 V AC, 240 V AC
-
65 kA IC at 277 V AC, 480 V AC, 600 V AC
-
-
Trip Functions: LSI (Long-time, Short-time, Instantaneous) with adjustable instantaneous + tracking short-time
-
Continuous Current Rated: Standard
-
Reverse Feed: Suitable for reverse feed
-
Lugs: TCLK365
-
Current Metering / Protective Relays: Not included
-
Special Markings: HACR
-
Standards: UL File #E11592, CSA File #LR40350
Key Features:
-
True RMS digital sensing—accurately evaluates both sinusoidal and non-sinusoidal (distorted) current waveforms
-
Adjustable instantaneous with tracking short-time as standard on all frames
-
Field-adjustable ampere rating via interchangeable rating plug
-
Current-limiting behavior (I²t limiting) protects downstream equipment
Materials & Construction: Molded-case housing; electronic trip unit with digital sampling; interchangeable front-mounted rating plug; TCLK365 terminal lugs.
Structural Features: 3-pole construction; front-mounted rating plug for on-site ampere rating changes; mechanical durability rated for a minimum of 10,000 no-load operations; electrical durability of 1,000–5,000 operations at rated current (depending on rating); short-circuit withstand of 5× rated interrupting capacity.
Working Principle: The digital, solid-state trip system continuously samples phase currents, computes the true RMS value, and compares it against the long-time, short-time, and instantaneous thresholds defined by the rating plug and trip-unit settings. When a threshold is exceeded for the corresponding time delay, the trip actuator opens the contacts, interrupting the fault current.
Application Scenarios:
-
Main incoming breakers for 600 V ac distribution systems
-
Feeder protection in industrial plants, commercial buildings, and utilities
-
Transformer primary protection (note: transformer inrush currents containing high 2nd-harmonic content can cause nuisance trips; coordination with the trip curve is essential)
Installation & Usage Notes:
-
Install per GE’s Spectra RMS MCCB documentation (e.g., GEA12171). Confirm the breaker ampere rating matches the application by selecting the proper rating plug.
-
For transformer protection, verify the breaker setting against NEC/IEC overcurrent coordination limits (e.g., 125 % of FLA without secondary protection, 250 % with).
-
Because the SGLA36AT0600 is a true-RMS electronic trip device, it responds to the heating effect of the current rather than the instantaneous peak—this mitigates nuisance trips on non-sinusoidal inrush but still requires proper coordination for high-magnitude symmetrical inrush (6–10× FLA).
-
Ensure proper torque on TCLK365 lugs (wire range per GE documentation).