Digital guide

You are here:

GE SGHC3601L3XX

  • Product Name:​ GE Spectra RMS™ Electronic Trip Molded Case Circuit Breaker
  • Introduction:​ The SGHC3601L3XX is a Spectra® RMS molded case circuit breaker equipped with a microEntelliGuard™ trip unit, providing flexible system protection, metering, and communication options for advanced electrical systems.

Detailed content

  • Technical Specifications:
    • Product Line: Spectra RMS – microEntelliGuard
    • Frame Type: SG600
    • Rated Current: 60 A, 80 A, 100 A, 125 A, 150 A
    • Number of Poles: 3
    • System Voltage: 120 V AC, 120/240 V AC, 240 V AC, 277 V AC, 480 V AC, 600 V AC
    • Interrupting Rating: 65 kAIC @ 120/240/277 V AC; 35 kAIC @ 480 V AC; 25 kAIC @ 600 V AC
    • Trip Function: LSI (Long-Time, Short-Time, Instantaneous)
    • Trip Indication Target: Yes
    • Continuous Current: Rated Standard
    • Suitable for Reverse Feed: Yes
    • Lugs: TCLK 365
    • Ground Fault: No
    • Current Metering: Yes
    • Communications: No
    • HACR: Yes
    • UL File #: E11592
    • CSA File #: LR40350
  • Features:​ Fully adjustable time-current curves (three long-time curve shapes: MVT I²t, CB, and Fuse I⁴t); optimal system coordination and protection; optional protective relays; standard metering capability; uses universal rating plugs and test kits common across the Spectra RMS family.
  • Material & Structure:​ Molded case construction; interchangeable trip style; microEntelliGuard trip unit.
  • Working Principle:​ The microEntelliGuard trip unit monitors current through adjustable long-time, short-time, and instantaneous functions to provide optimal system coordination and protection, with the ability to trigger trip indication targets when faults occur.
  • Application Scenarios:​ Advanced electrical systems requiring flexible system protection, metering, and communication options.
  • Installation Requirements:​ Bolt-on mounting type; suitable for reverse feed applications; professional electrical installation required.
  • Usage Notes:​ Ensure the rated current matches the application; verify interrupting rating matches the system voltage; only qualified personnel should perform installation and maintenance.

You may also like