Detailed content
-
Types: Pt100, Pt1000, Ni120, Cu10
-
Lead Compensation: Automatic 3-wire
-
Accuracy: ±0.1 % or ±0.5 °C (whichever greater)
-
Isolation: 1500 V DC
-
Filtering: 50/60 Hz hardware notch
-
Terminals: Barrier screw type
-
Temperature: −40 °C to +85 °C (board), 0–60 °C (typical cabinet)
Functional Features: Open-circuit detection, per-channel software enable, noise-immune front-end.
Working Principle: Constant-current excitation → voltage across RTD → ADC → linearization → backplane.
Materials: FR-4 conformal-coated PCB, brass barrier terminals.
Installation: Mount in Mark VI thermo I/O group; use 3-wire twisted cable; bond shield at one end.
Precautions: Do not substitute 2-wire sensors without rewiring; avoid running RTD cables parallel to 480 VAC trays.