Detailed content
-
Types: J, K, E, T, S, R, B (per channel config)
-
Input Span: -8 mV to +45 mV
-
Resolution: 16 bit
-
Cold Junction Comp: onboard CJC sensor per bank
-
Isolation: 1500 V DC channel-to-backplane
-
Power: from IONet pack bus (24 V derived)
-
Temp Range: -30 °C to +70 °C
Functional Features: Per-channel open-wire detection, CJC fault alarm, 50/60 Hz digital filtering, auto-scaling to °C/°F in controller.
Application Scenarios: Gas turbine exhaust spread, generator bearing temp, HRSG header temp.
Material Composition: FR4 PCB, instrument-grade instrumentation amp, gold contact backplane.
Structural Characteristics: Mark VIe pack form, RJ45 IONet, no front terminals (remote TB).
Working Principle: TC millivolts amplified → offset by CJC → 16-bit ADC → linearized to temperature → published to controller.
Installation Requirements: Use shielded twisted pair, ground shield at terminal board only.
Usage Notes: Never land millivolt source with common-mode > isolation rating; keep CJC unobstructed.