Detailed content
Technical Specifications:
-
Channels: 8 independent RTD inputs
-
Sensor Types: Pt100, Cu100, Ni120, 10–3200 Ω
-
Resolution: 14-bit
-
Accuracy: ±0.5 °C typical (Pt100)
-
Isolation: 2500 V AC channel-to-backplane
-
Bus: IONet (10/100 Mbps deterministic Ethernet)
-
Power: From I/O pack backplane, 24 V DC nominalFunctional Features: 2-wire/3-wire selectable; open-circuit detection; high-noise rejection; auto linearization; front LED per channel.Materials & Structure: Conformal-coated FR-4; metal faceplate; RJ-45 IONet jack; detachable terminal block.Working Principle: Constant current source excites RTD; voltage drop digitized and converted to temperature via curve table; result published on IONet at control scan rate.Installation Requirements: Snap into IS220 I/O pack base; shield drain to single point; keep RTD leads away from VFD cables.Precautions: 3-wire RTD must use matched lead lengths; never mix Pt100 and Cu100 on same module without re-config; avoid loop resistance > cable spec.