Detailed content
Technical Specifications:
-
Protocol: PROFIBUS DP V0/V1 Class 1 Master, IONet 10/100 Mbps
-
Interfaces: 2 × RJ45 IONet, 1 × DE-9 RS-485
-
Baud: 9.6 kbps – 12 Mbps auto-sense
-
Slaves: Up to 125 DP slaves
-
Processor: 32-bit RISC, 8 MB SDRAM, 16 MB Flash, Hilscher COM-C ASIC
-
Power: 27.4-28.6 V DC nominal 28 V DC, 0.18 A
-
Isolation: 2500 V AC field-backplane – Temperature: -20 °C to +55 °C
-
Hazardous: Class I Div 2, ATEX/IECEx Zone 2Functional Features: Redundant IONet, galvanic isolation, slave polling, I/O table mapping, bus diagnostics via front LEDs.Structural Characteristics: Compact 110 × 60 × 67 mm plastic housing, snap-in to I/O pack, optional IS200SPIDG1A ID board.Working Principle: Mark VIe sends control table over IONet → RISC maps to DP frames → Hilscher PHY polls slaves → responses repacked to IONet.Installation Requirements: Mount in Mark VIe I/O pack base, terminate RS-485 with 220 Ω ends, use shielded PROFIBUS cable.Usage Notes: Do not power with 24 V DC source not meeting 28 V DC tolerance; verify DP slave GSD files before commissioning.