GE IS220PDOAH1A
Product Name: Mark VIe 12-Channel Relay Output Pack (Discrete Output Pack)
Product Overview: A “pack-style” discrete output module used inside GE Mark VIe Speedtronic turbine and compressor control cubicles. It combines 12 relay outputs (Form-C contacts) with an embedded processor and dual 100 Mb Ethernet ports on one card, allowing the controller to drive medium-power field devices without external interposing relays. The pack sits at the “field-actuator” layer, receiving output commands over the I/O Ethernet network, time-stamping the data, energizing the appropriate relays, and returning contact-status feedback to the controller.
Detailed content
Key Specifications:
-
Outputs: 12 Form-C relay contacts
-
Field Voltage: 24 VDC nominal (12–48 VDC/AC supported)
-
Load Current: 3 A per channel max, 4 A total (field-fused)
-
Logic Supply: 24 VDC via 3-pin backplane feed
-
Response Time: ≈ 6 ms (Ethernet command to contact closure)
-
Ethernet: Dual 100 Mb full-duplex RJ45 ports with on-board switch
-
Isolation: 1500 V optical between field and logic
-
Diagnostics: Front-panel LEDs, infrared serial port for local interrogation
-
Terminal Boards: Compatible with TRLYH1B/C/D/F (magnetic relays) or TRLYH1E (solid-state)
-
Operating Temperature: –40°C to +70°C (variant dependent)
-
Storage Temperature: –55°C to +85°C
-
Relative Humidity: 5%–95% non-condensing
-
Weight: 120 g (some configurations up to 640 g)
-
Dimensions: 3.25″ H × 1.65″ W × 4.78″ D
-
Memory: Flash and RAM
-
LEDs: Four (Power, Attention, TxRx, Link)
-
Hazardous Location: Certified for Zone 2
Core Features:
-
12-relay density: one pack replaces multiple interposing relays, freeing Mark VIe slots
-
Dual Ethernet redundancy: two 100 Mb ports with internal switch for redundant network paths
-
On-board processor & diagnostics: local CPU time-stamps commands and validates contact status — welded relays or open coils are reported immediately (essential for overspeed or fire-gas protection loops)
-
TRLY terminal-board compatibility: plugs straight onto TRLY boards, no external 24 V wiring beyond the terminal board
-
Zone 2 / marine certification: can be landed in hazardous locations without additional isolation barriers
Application Scenarios:
-
Combined-cycle power plants: installed in the “auxiliary output” section of Mark VIe panels governing gas turbines
-
Drives 24 VDC lock-out valves, cooling-fan contactors, and fire-protection solenoids while reporting contact status back to the turbine controller
-
Compressor stations and offshore platforms (Zone 2 certified)
Installation & Usage Notes:
-
Plugs directly onto a Mark VIe terminal board (TRLYH1B/C/D/F for magnetic relays or TRLYH1E for solid-state)
-
No external 24 V wiring required beyond the terminal board
-
Transformer-isolated logic keeps the 24 VDC field side separate from the 5 V backplane
-
Use front-panel LEDs and infrared port for local diagnostics
-
Verify relay assignments and field voltage (12–48 VDC/AC) match application before energizing