Technical Specifications: 24-channel input; supports Type J, K, E, S, and T thermocouples; 16-bit analog-to-digital conversion resolution.
-
Functional Features: Includes automatic cold junction compensation (CJC), open thermocouple detection, and software linearization.
-
Application Scenarios: Critical for monitoring exhaust temperatures in gas turbines (TTRX) and bearing temperatures in generators.
-
Performance Parameters: Accuracy within ±1°C; fast scanning capabilities to capture rapid temperature transients.
-
Structural Characteristics: Multi-layer PCB with surface-mount technology (SMT); equipped with high-reliability terminal blocks.
-
Installation Requirements: Must be installed in a VME rack with proper air flow; ensure shielded twisted-pair wiring for thermocouple runs.
-
Usage Notes: Verify jumper settings match the thermocouple type being used; avoid routing thermocouple wires near high-voltage cables to prevent induced noise.