Solenoid supply: Positive DC to up to 3 trip solenoids
-
Companion board: TRPG provides negative side
-
Power input: JZ1 connector feeds feedback and economizer relays
-
Coating: Conformal PCB coating
-
Read-only ID chip: Stores serial, revision, plug position
-
Functional Features: 2-out-of-3 or 2-out-of-2 voting depending on system config, FlashDrop-capable parameter transfer on some variants, direct wired AND with VPRO protection module.
-
Application Scenarios: Heavy gas and steam turbine emergency overspeed/stop protection in Mark VI control rooms.
-
Installation Requirements: Secure in TREG rack slot, separate positive/negative solenoid wiring, verify JZ1 orientation, test trip path with injected signal before turbine roll.
-
Usage Notes: Never bypass economizer relay; verify relay contact resistance annually; H5B is not a drop-in for H1B without cabinet rewiring review.