GE IS200TPROH2C
Product Name: Mark VIe HART-Enabled Analog I/O Module (PHRA I/O Pack)
Product Introduction: The IS200TPROH2C is a HART-enabled analog input/output module developed by General Electric for the Mark VIe control system. It serves as a critical connection point, providing electrical interfaces between one or two I/O Ethernet networks and analog input/output terminal boards. It combines a standardized processor board (common to all Mark VIe distributed I/O packs) with a customized acquisition board optimized for analog input functionality.
Detailed content
Technical Specifications:
-
Manufacturer: General Electric
-
System: Mark VIe Distributed I/O
-
Analog Inputs: Up to 10 analog input channels
-
Analog Outputs: 2 channels of 4–20 mA current loop
-
HART Communication: Supported in 4–20 mA mode, relaying HART messages between field devices and AMS
-
Network Interface: Dual RJ45 Ethernet connectors for redundant I/O Ethernet
-
Power Input: 3-pin connector
-
Output Connection: DC-62 pin connector to terminal board
-
Diagnostics: LED indicators for visual diagnostics; infrared port for local serial diagnostic communication
-
Mounting: Terminal board mounted I/O pack
Functional Features:
-
Powerful analog input management for up to 10 channels
-
Current loop input sensing via load terminal resistor on the terminal board
-
Two 4–20 mA current loop outputs for control signals
-
HART message relay between HART-enabled field devices and Asset Management Systems
-
Flexible connectivity — HART field devices can be connected through any input or output
-
Dual Ethernet redundant connectivity
-
Local diagnostics via infrared serial port
Material Composition & Structure:
-
Combination of a standardized Mark VIe processor board and a customized analog acquisition board
-
Dual RJ45 Ethernet ports
-
3-pin power connector
-
DC-62 pin connector for terminal board mating
-
Onboard LED status indicators
-
Infrared diagnostic port
Working Principle: The PHRA I/O pack inserts directly into the selected terminal board. The dual Ethernet ports connect to the Mark VIe I/O network(s), providing redundant communication paths. The customized acquisition board conditions and digitizes up to 10 analog input signals. For current loop inputs, the voltage across the load terminal resistor on the terminal board is sensed and measured. The two 4–20 mA outputs are driven by the DAC stage. In HART mode, the module modulates/demodulates HART signals on top of the 4–20 mA loop, relaying digital HART frames between the field instrument and the host AMS via the Ethernet network. The 150 MHz-class processor handles scaling, linearization, and HART protocol stack.
Installation Requirements:
-
Securely install the selected terminal board in its desired position
-
Insert a single PHRA I/O pack directly onto the terminal board connector
-
Use the threaded bolts near the Ethernet port to secure the I/O pack to the terminal board’s mounting brackets
-
Adjust the bracket position to prevent right-angle force on the DC-62 pin connector (one-time adjustment)
-
Connect one or two Ethernet cables; in dual configuration, typically ENET1 connects to the R controller-associated network
-
Insert the side power connector to energize the pack
Usage Precautions:
-
Ensure the DC-62 connector is fully seated before securing bolts to avoid pin bending
-
Verify network redundancy cabling matches the controller topology
-
Use the infrared port for deep diagnostics — do not attempt to remove the conformal coating if present
-
Monitor LED indicators for power and channel health