Product Name:​ GE Fanuc Field Control Analog Output Module (IC670ALG320)
Introduction:​ The IC670ALG320 (with suffix K) is a 4-channel analog output module designed for the GE Fanuc Field Control I/O system. It converts digital control signals from a host processor into precise analog current or voltage outputs for controlling industrial actuators, valves, dampers, and positioners. (Note: The “K” suffix designation specifics are not detailed in available public documentation; the base IC670ALG320 specifications are provided.)

Detailed content

Technical Specifications:
  • Manufacturer: GE Fanuc
  • Series: Field Control
  • Channels: 4 (Four independent sourcing outputs)
  • Output Signal Options: 0-20 mA, 4-20 mA, 0-10 VDC, 0-12.5 VDC
  • Digital Resolution: 12 bits
  • Analog Resolution: 4.0 µA @ 4-20 mA, 50 µA @ 0-20 mA, 2.5 mV @ 0-10 VDC, 3.125 mV @ 0-12.5 VDC
  • Conversion Time: 60 microseconds per channel (typical)
  • External Power Supply: 20-29 VDC (24 VDC nominal), maximum ripple 5%
  • Current Consumption: 80 mA standby, 180 mA operating (including loop current)
  • Power Dissipation: 1.4 W minimum to 4.3 W maximum
  • Isolation: 1500 VAC for 1 minute (ground to logic), 250 VAC continuous
  • Temperature Coefficient: ±0.002% of value per °C (typical)
  • Linearity: 1 LSB resolution value
  • Operating Temperature: 0°C to 60°C
  • Weight: 0.26 kg (approx.)
Functional Features:
  • Four independent sourcing channels for current or voltage output
  • Configurable output ranges via external jumper links or internal registers
  • Integrated EMI filtering and ground isolation
  • Front-panel LED indicators for monitoring field power and backplane bus status
  • Single-ended wiring for simplified integration
Structural Characteristics:​ The module is a Field Control I/O module with 4 channels grouped as a single group, designed for DIN-rail or rack mounting in the Field Control system.
Working Principle:​ The module receives digital signals from the host processor via the Bus Interface Unit (BIU), converts them to analog values using a 12-bit DAC, and sources the current/voltage to field devices.
Installation Requirements:
  • Ensure system power is disconnected before installing or removing
  • Use instrumentation-grade shielded twisted-pair cabling
  • Verify external 24 VDC power supply is within 20-29 VDC range
  • Configure output ranges using jumper settings before applying power
  • Maintain proper ventilation (dissipation up to 4.3 W)
Usage Notes:​ Compatible with Field Control and Rx7i PACSystems architectures. Install in a clean, dry environment free from conductive dust and liquid ingress.