Product Name:​ GE Mark VIe Power Supply Module (Standard Type)
Product Overview:​ The DS3820PS1B1B1A is a standard power supply module in the GE Mark VIe system, providing stable DC operating voltage for I/O modules within the rack.
Technical Specifications:
  • Input Voltage: 120 VAC / 240 VAC (selectable), 50/60 Hz

Detailed content

  • Input Range: 85 VAC to 264 VAC (full range)
  • Output Voltages: +5 VDC / +24 VDC / +5 VSB (standby)
  • +5 V Output Current: 10 A (max)
  • +24 V Output Current: 5 A (max)
  • Total Output Power: Approx. 170 W
  • Efficiency: ≥ 85% (typical)
  • Protection: OVP / OCP / SCP / OTP
  • Operating Temperature: 0°C to +55°C
  • Cooling: Natural convection
  • Dimensions: VME64 standard size
Functional Features:
  • Suitable for small to medium Mark VIe systems with lower I/O count
  • Supports redundant configuration (dual-module parallel)
  • Front panel with Power OK LED and Fault LED
  • Online fault alarm and status reporting
  • Hot-swappable (when system permits)
Structural & Material Features:
  • VME64 standard PCB card (160 mm × 233.4 mm)
  • Front panel: AC input terminals, DC output terminals, ground terminal
  • Top: Status indicator LEDs
  • Bottom: DIN 41612 European connector
  • PCB: FR-4 epoxy fiberglass board
  • Transformer: Ferrite core, copper wire winding
  • Rectifier Bridge: Industrial-grade rectifier module
  • Capacitors: 105°C rated electrolytic capacitors
Application Scenarios:​ Thermal power plants, gas turbine control, petrochemical process control, water treatment, small-to-medium industrial DCS.
Installation Requirements:
  • Install in Mark VIe VME rack standard slot
  • AC input must connect through UPS or voltage stabilizer
  • Redundant configuration must connect the current sharing cable
  • Ground resistance ≤ 4 Ω
Usage Notes:
  • Confirm input voltage setting matches field power supply
  • Strictly prohibit short circuit at output
  • Module address set via hardware or software
  • On failure, check LED status and refer to fault codes for troubleshooting