Digital guide

You are here:

GE DS3800NMEA1G1E

Product Name:​ GE Mark VIe DS3800 Series Multi-Function Ethernet Analog Input I/O Module
Product Overview:​ The DS3800NMEA1G1E is documented as a non-redundant, multi-function, Ethernet-based analog input I/O module belonging to the DS3800 series intelligent I/O pack for GE Vernova (formerly GE Power) Mark VIe Distributed Control Systems. It is dedicated to analog signal acquisition for gas turbines, steam turbines, generators, and auxiliary systems.

Detailed content

Technical Specifications:
  • Series:​ GE Mark VIe DCS / DS3800 I/O pack
  • Configuration:​ N = Non-Redundant; M = Multi-Function; E = Ethernet; A1 = Analog Input Group 1; G1 = Revision G1; E = Version E
  • Input Channels:​ 16 channels (typical)
  • Input Signal Types:​ 4–20 mA / 0–20 mA / 0–10 V / ±10 V (software-configurable)
  • Resolution:​ 16-bit A/D
  • Sampling Rate:​ 10 ms per channel (100 Hz)
  • Accuracy:​ ±0.1% Full Scale
  • CMRR:​ ≥ 100 dB (50/60 Hz)
  • Isolation:​ Channel-to-channel and channel-to-ground, 1500 VDC
  • Communication:​ 10/100 Base-T Ethernet (RJ45), UDP/IP (Mark VIe protocol)
  • Power Supply:​ 24 VDC (bus-powered)
  • Power Consumption:​ ≤ 5 W
  • Operating Temperature:​ 0–60 °C
  • Protection Class:​ IP20 (panel/cabinet installation)
  • Certifications:​ CE, UL, ATEX (optional for hazardous areas)
Material Composition:​ 6-layer FR-4 high-Tg PCB with conformal coating; Industrial-grade 16-bit ADC (Analog Devices / TI); optocoupler + magnetic isolation devices.
Functional Features:​ Supports RTD (Pt100/Pt1000) and thermocouple (J/K/T/E/N/R/S/B) inputs (model-dependent); built-in sensor open-wire detection and over-range alarm; remote calibration (no on-board potentiometers); LED status indicators; hot-swappable (subject to controller support).
Working Principle:​ Field analog signals enter the module, are galvanically isolated, and digitized by the 16-bit A/D converter. The FPGA buffers and packets the data, then transmits it over Ethernet (UDP/IP) to the Mark VIe controller for processing.
Application Scenarios:​ Analog signal acquisition for gas turbines, steam turbines, generators, and balance-of-plant auxiliary systems in power generation.
Installation Requirements:​ Install inside a control cabinet (IP20 environment). Connect 24 VDC bus power and RJ45 Ethernet to the Mark VIe network. Observe correct polarity and shield grounding per Mark VIe wiring standards.
Usage Notes:​ Do not exceed 60 °C ambient. Verify channel configuration in the Mark VIe engineering tool matches the field wiring. Use only in cabinet environments with proper ventilation.