GE DS3800NASB1B1C
Product Overview & Core Function
This board provides 8 high-speed analog input channels and 8 analog output channels, both with 16-bit resolution. It is engineered for specialized sensor and actuator interface applications in demanding industrial environments, particularly where standard boards fail due to thermal drift. The 1B1C suffix is a mixed-grade coating configuration: “B” indicates medium-duty conformal coating on the board itself (30–50 microns), while “C” indicates heavy-duty coating on the termination hardware (40–60 microns) for moderate chemical exposure resistance.
Detailed content
Technical Specifications
- Manufacturer: GE Energy / GE Automation
- Series: Speedtronic Mark V
- Analog Inputs: 8 channels, differential or single-ended
- Analog Outputs: 8 channels, configurable voltage or current
- Input Resolution: 16-bit (0.3 mV per count on 10 V range)
- Output Resolution: 16-bit (0.3 mV per count on 10 V range)
- Input Range: 0–10 VDC or 4–20 mA (jumper-selectable)
- Output Range: 0–10 VDC or 4–20 mA (jumper-selectable)
- Input Impedance: >1 MΩ (voltage); 250 Ω (current)
- Output Load: >2 kΩ (voltage)
- Input Accuracy: ±0.1% of full scale (including drift)
- Output Accuracy: ±0.1% of full scale (including drift)
- Settling Time: 1 ms
- Signal Conditioning: Programmable excitation (5 V or 10 V), bridge completion, and programmable filtering for noise rejection
- Isolation: Channel-to-ground, 1500 VDC
- Operating Temperature: –40 to +85 °C (extended); datasheet base rating 0 to +60 °C
- Storage Temperature: –40 to +85 °C
- Backplane Power: +5 VDC
Functional Features
- Built-in signal conditioning for specialized sensors
- Mixed-grade coating: medium-duty on board, heavy-duty on terminations
- Field-configurable for 0–10 V or 4–20 mA
- Programmable excitation, bridge completion, and filtering
Application Scenarios
Designed for demanding industrial environments within turbine control rooms and similar installations where extended temperature performance is required. The board is particularly suited for specialized sensor and actuator interface applications.
Installation & Usage Notes
- Verify jumper configuration for voltage or current mode before applying field signals.
- Ensure proper conformal coating integrity during handling.
- This is an end-of-life Mark V series board; limited stock remains.
- Observe ESD precautions when handling.