Product Name:​ Mark IV DCMB Digital Communication Module
Product Introduction:​ Serial communication and control-logic board in Mark IV; exchanges data with external meters, recorders, or peer controllers.
Technical Specifications:
  • Ports: 2 independent serial (Port A / Port B)

Detailed content

  • Standards: RS-232C, RS-485
  • Baud: 300 bps – 115.2 kbps
  • Protocols: Modbus RTU, ASCII, GE GENIUS Bus
  • Isolation: 2500 V DC serial-to-backplane
  • Power: +5 V / +24 V from Mark IV rack
  • Indicators: TXDA, RXDA, DTSA, CDA LEDs
  • Jumpers: 7 configuration
Functional Features:​ EPROM-based control code, watchdog, redundant comms option, onboard UART framing.
Application Scenarios:​ Link Mark IV to HMI, data historian, or third-party protection relay.
Material Composition:​ FR4, UART ICs, opto-isolators, EPROM sockets.
Structural Characteristics:​ 40-pin + 20-pin headers, DIP switches, extractor arms.
Working Principle:​ Controller writes message to UART → framed per protocol → driven to field device; reply parsed back to Mark IV memory.
Installation Requirements:​ Terminate RS-485 both ends with 120 Ω; isolate serial shield.
Usage Notes:​ Baud and parity must match remote device exactly; do not swap Port A/B without config change.