Detailed content
-
Input: dry contact or 24 V DC (18–30 V = 1, 0–6 V = 0)
-
Current: ≤ 2 mA/ch
-
Response: ≤ 10 ms
-
Isolation: 500 V DC ch-ch and ch-backplane
-
Debounce: 1–100 ms software filter
-
Event Capture: 1 ms timestamp
-
Power: +5 V from backplane, ≤ 2 W
Functional Features: NO/NC per channel, optical isolation, wire-break flag, front LED per channel.
Application Scenarios: Limit switches, pushbuttons, breaker aux contacts, pump-run status in Mark IV panels.
Material Composition: FR4 high-Tg, Toshiba/Vishay optocouplers, spring terminals, zinc-alloy faceplate.
Structural Characteristics: 3U Eurocard, 32 LEDs (2×16), 64-pin VME backplane, top latch.
Working Principle: Contact close → current through opto LED → transistor side toggles → scanned by logic → timestamped.
Installation Requirements: Spring terminal torque 0.5 N·m; backplane fully seated before +5 V.
Usage Notes: Wet 24 V must come from isolated field supply, not backplane 5 V.