Digital guide

You are here:

GE DS200TCEAG2BSF

GE DS200TCEAG2BSF is a Mark VI-series TCEA-type protection and signal-conditioning board used in GE turbine control systems for emergency overspeed protection and critical signal processing.
  • Technical Specifications
    • Input Impedance: >1 MΩ

Detailed content

    • Operating Temperature: 0°C to 60°C
    • Storage Temperature: -40°C to 85°C
    • Relative Humidity: 5% to 95% non-condensing
    • Shock Resistance: 15 g peak (IEEE 344)
    • Vibration Resistance: 0.5 g RMS, 5 Hz–200 Hz (IEEE 344)
    • EMC Compliance: IEC 61000-6-2 industrial immunity
    • Enclosure: Die-cast aluminum alloy with powder-coat finish
    • PCB: FR-4 multilayer with conformal coating
    • Dimensions: ≈25 mm × 120 mm × 140 mm (W × H × D)
  • Functional Characteristics
    • Cold-junction compensation (CJC) for thermocouple signal acquisition
    • Open-circuit and short-circuit detection with automatic alarm
    • Signal Quality Monitor for real-time signal integrity assessment
    • Configurable 50 Hz / 60 Hz notch filter per channel
    • Hot-swappable replacement without affecting adjacent modules
  • Structural Features
    • 8 channel-status LEDs on front panel
    • 32-pin high-density D-type rear connector for backplane bus
    • DIP switch on top for address and configuration selection
    • Spring-type screw terminals, nickel-plated
  • Application Scenarios
    • Gas turbine generator control
    • Steam turbine generator control
    • Industrial gas turbine compressor drives
    • Petrochemical process control
  • Installation Requirements
    • Install in designated slot of GE Mark VI terminal base (e.g., TKMA31000WL)
    • Use shielded twisted-pair wiring; shield grounded at single point
    • Separate analog and digital signal cables by ≥100 mm
    • Set module address via DIP switch, range 0–7; no duplicate addresses on same base
  • Usage Notes
    • Do not exceed 30 V DC or 25 mA input to avoid A/D converter damage
    • Enable cold-junction compensation for thermocouple inputs to prevent >10°C measurement error
    • Execute channel calibration via ToolboxST software at 12-month intervals
    • On module fault, corresponding channel automatically holds last valid value