GE AEU3422RCXAXT1B4
- Product Name: GE Pro-Stock A-Series II 3-Phase Interior, Unassembled Lighting Panelboard
- Product Introduction: The AEU3422RCXAXT1B4 is a 3-phase interior assembly (unassembled) from GE’s A-Series II panelboard line, configured for 277/480 VAC lighting and power distribution. The “AEU” prefix denotes A-Series, 480Y/277 V, 3-phase; “3422” denotes 225 A frame, 42 circuits; “RC” denotes copper bus, feed-through; “XAX” denotes convertible (top or bottom feed) with no main included; “T1” denotes a specific trim configuration; “B4” denotes a box/front height of 49.5 inches.
Detailed content
- Technical Specifications:
- Amperage Rating: 225 A
- Voltage Rating: 277/480 VAC, 3-phase
- Number of Poles: 3
- Number of Circuits: 42
- Feed Type: Feed-through
- Bus Material: Copper
- Mounting Type: Bolt-on
- Enclosure Type: NEMA 1 / 3R / 12
- Box/Front Height: 49.5 in
- Dimensions: 53-1/2 in L × 15-1/4 in W × 49-1/2 in H
- Package Weight: 30.8 lb
- Series: A-Series II
- Type: 3-Phase Interior, Unassembled
- Functional Features:
- Maximum system voltage up to 480 VAC for AE panelboard line
- Field-installable kits for neutral and sub-feed breaker additions
- All panels convertible between main lug or main breaker
- Reversible interior — no need to specify top or bottom feed
- Solid-state Spectra RMS or thermal-magnetic breakers available as mains or sub-feeds
- Flush or surface mounted trims with door-within-door and front-hinge-to-box options
- Modular kits for field installation of 200% neutrals and service entrance bonding straps
- Field-installable TVSS kits, 200 kA per phase
- Up to 3 poles of sub-feed available in 225 A frames
- Application Scenarios: Electrical distribution and control applications; commercial and industrial buildings requiring 277/480 V 3-phase power distribution for lighting and equipment
- Material Composition: Copper bus; steel enclosure; reversible interior assembly with bolt-on mounting
- Structural Features: Unassembled interior kit; convertible feed orientation; reversible interior; supports up to 6 poles of sub-feed (in 400 A and 600 A frames) or 3 poles (in 225 A frames)
- Installation Requirements:
- Install in accordance with NEC Article 384 and UL 67
- Verify enclosure type (NEMA 1/3R/12) suits the installation environment
- Properly bond grounding and bonding straps per NEC
- For service entrance applications, install service entrance bonding straps
- Torque all bolt-on connections to GE-specified values
- Usage Notes:
- ARRA Compliant, Buy American Act Compliant, RoHS Compliant
- CSA Certified; California Building Code Seismic Zone 4; International Building Code Seismic Zone 3 and 4
- UL 67, UL 50, UL 943 listed
- Extruded split neutrals speed and simplify wiring