The GE 173C8413BDG02 is a 4-channel analog input module for the GE Mark VI / Mark VIe distributed control system (DCS). It receives standard 4-20 mA or 0-10 V signals with independent galvanic isolation per channel, used for acquiring process variables such as temperature, pressure, flow, and level.
Technical Specifications
  • Channels:​ 4

Detailed content

  • Input Signal:​ 4-20 mA two-wire / 0-10 V (configurable)
  • A/D Resolution:​ 16-bit
  • Accuracy:​ ±0.1% full scale
  • Inter-channel Isolation:​ 1500 VDC continuous
  • CMRR:​ ≥ 120 dB at 50/60 Hz
  • Input Impedance:​ 250 Ω (current mode), 1 MΩ (voltage mode)
  • Sampling Rate:​ 250 ms/channel typical
  • Power:​ 5 VDC and 24 VDC from Mark VI rack backplane
  • Power Consumption:​ ≤ 2 W per module typical
  • Operating Temperature:​ 0°C to 60°C
Functional Features
  • Four fully isolated channels with no inter-channel interference
  • Open-wire detection; automatically flags faults on input loop break
  • Sensor fault detection (HART-capable variants supported)
  • Front-panel LED status indicators
  • Hot-standby redundancy support
  • Online insertion/removal without affecting other channels
Structural Characteristics
  • Standard Mark VI I/O module form factor
  • Plug-in installation with hot-swap support
  • Front-panel programmable jumpers and LED indicators
  • Rear backplane: Mark VI standard high-speed serial bus interface
  • Bottom signal terminal strip
Installation Requirements
  • Install in a standard Mark VI I/O rack
  • Use shielded twisted-pair signal cables with shield single-point grounded at the control room end
  • Rack ground resistance ≤ 4 Ω
  • Ambient temperature 0°C to 60°C, relative humidity 5% to 95% non-condensing
Usage Precautions
  • In current mode, never connect signal lines in parallel
  • In voltage mode, the 1 MΩ input impedance requires verification of signal source drive capability
  • In redundancy configuration, the two modules must be addressed as a redundant pair
  • Confirm rack power is stable before energizing the module