GE 173C8413BAG01
Product Name: GE Mark V / Mark VI Gas Turbine Control Analog Input Module
Overview:
The 173C8413BAG01 is an analog input (AI) module supplied by GE Energy for Mark V and Mark VI gas turbine control systems. It acquires analog signals such as temperature, pressure, and vibration during gas turbine operation, serving as a core I/O component of the turbine control system.
Detailed content
Technical Specifications:
-
Series: Mark V / Mark VI Speedtronic I/O Module
-
Channels: 16-channel analog input
-
Signal Types: 4–20 mA / 0–10 V DC (configurable)
-
Resolution: 16-bit A/D conversion
-
Sampling Rate: 100 ms/channel (all channels)
-
Accuracy: ±0.1% full scale
-
Isolation Voltage: 500 V DC (between channels)
-
Communication: GE control system internal bus (Genius / Series 90-70)
-
Supply Voltage: 5 V DC (bus-powered)
-
Operating Temperature: 0°C to +60°C
-
Storage Temperature: -40°C to +85°C
Features:
-
High-precision 16-bit A/D conversion
-
Channel-to-channel isolation to eliminate crosstalk
-
Cold junction compensation (for thermocouple input models)
-
Wire-break detection and over-limit alarm
-
Hot-swappable module support (Mark VIe system)
-
Status LED indicating per-channel working state
Material Composition:
-
PCB: 6-layer FR-4 glass fiber board with gold finger connector
-
Module Housing: Galvanized steel plate + conductive paint (EMC shielding)
-
Connector: Military-grade high-density connector
-
A/D Chip: Industrial-grade Δ-Σ converter
Working Principle:
Analog signals pass through signal conditioning circuitry (filtering, amplification, isolation) and enter the 16-bit Δ-Σ A/D converter. Conversion results are optically isolated and sent to the control system internal bus for CPU processing in gas turbine speed control, temperature monitoring, and load regulation.
Applications:
Gas turbine power generation, combined-cycle power plants, industrial drive turbines, oil and gas transmission.
Installation Requirements:
-
Insert into designated Mark V/VI control cabinet slot
-
Tighten module fixing screws to 1.5 N·m torque
-
Use shielded twisted-pair cables for signal wiring, single-point grounding
Precautions:
-
Strictly prohibit hot-swapping (Mark V system); Mark VIe supports hot-swap
-
Maintain ≥ 100 mm separation between signal and power cables
-
Perform accuracy calibration every 5 years
-
Store backup modules in anti-static packaging, humidity ≤ 60% RH