Digital guide

You are here:

GE 104X106MAG01

Product Name:​ GE Fanuc 90-30 / 90-70 Series Analog Input Module
Product Introduction:​ This module is an analog input I/O module designed by GE Digital (formerly GE Fanuc Automation) for the 90-30 / 90-70 programmable logic controller (PLC) series. It provides 16 independent analog signal acquisition channels for distributed control systems, SCADA data acquisition, and industrial process control.

Detailed content

Technical Specifications:
  • PLC Series:​ GE Fanuc 90-30 / 90-70
  • Module Type:​ 104X Series Analog Input Module
  • Channels:​ 16 channels
  • Signal Types:​ 4–20 mA current / 0–10 V voltage (configurable per channel)
  • Resolution:​ 12-bit A/D conversion (4096 levels)
  • Sampling Rate:​ 10 ms per channel (fastest)
  • Accuracy:​ ±0.1% of full scale (including linearity, gain, and offset errors)
  • Input Impedance:​ 250 Ω (current mode) / 1 MΩ (voltage mode)
  • Isolation:​ Channel-to-channel isolation; module-to-backplane bus isolation
  • Power Supply:​ +5 V DC (provided by PLC backplane)
  • Power Consumption:​ Typical 2.5 W
  • CMRR:​ >100 dB at 50/60 Hz
  • Channel Crosstalk:​ < -80 dB
  • Operating Temperature:​ 0°C to +60°C
  • Storage Temperature:​ -40°C to +85°C
  • Humidity:​ 5%–95% RH (non-condensing)
  • Vibration:​ Complies with IEC 60068-2-6
Structural & Material Features:
  • Module Housing:​ Flame-retardant ABS engineering plastic, UL94 V-0 rated
  • PCB:​ FR-4 glass fiber epoxy board with conformal coating (moisture/anti-corrosion/anti-fungal treated)
  • Connectors:​ Military-grade gold-plated pins, hot-swappable supported
  • Terminal Block:​ Screw-clamp type, suitable for 14–28 AWG wire
Key Features:​ Per-channel independent configuration (current or voltage input); automatic wire-break detection with DI status reporting; programmable signal range calibration; built-in cold-junction compensation (for thermocouple variants); per-channel over/under-voltage and wire-break diagnostics.
Application Scenarios:​ DCS distributed control systems; SCADA data acquisition; industrial process control; temperature, pressure, flow, and level monitoring in manufacturing, power, and chemical processing.
Installation & Usage Notes:​ Ensure +5 V DC backplane power is stable; configure each channel’s signal type via software; verify proper grounding to maintain >100 dB CMRR; perform periodic calibration checks to maintain ±0.1% accuracy; replace module only with power removed unless hot-swap is explicitly supported by the specific 90-70 rack configuration.