GE 0996D957G0001
Product Name: Mark V Serial Communication Interface Module (COMM)
Introduction: Asynchronous serial gateway enabling Mark V controller to talk Modbus, SRTP, DNP3 with external SCADA/HMI/meters.
Technical Specifications:
-
Ports: 1× RS‑232 DB9, 1× RS‑485 screw terminal
Detailed content
-
Isolation: 500 VDC port‑to‑port optical isolation
-
Baud: 300–38400 bps software set
-
Protocols: Modbus RTU/ASCII, GE SRTP, DNP3.0
-
Parity: None/Even/Odd/Mark/Space
-
Power: 5 VDC backplaneFunctional Features:
-
Independent buffers per port
-
Watchdog on message timeout
-
LED TX/RX per portWorking Principle: Serial frames converted to Mark V internal memory map objects, polled/responded by controller application.Structure: Compact card, DB9 bracket + terminal header.Installation: Install in VME communication slot, terminate RS‑485 with 120 Ω at ends, avoid parallel run with 600 V cables.Precautions: Wrong baud or parity = silent comms; RS‑485 bias resistors required on long runs.