Emerson SS4310T01
Product Overview
The SS4310T01 is a safety digital input CHARM module from Emerson’s DeltaV SIS / SLS 1508 platform. It belongs to the DeltaV Electronic Marshalling CHARMs I/O family as a logic-solver safety CHANNEL (LS-CHARM), providing intrinsically safe, SIL 3-rated acquisition of discrete field signals for safety instrumented functions. It collects dry-contact or wet-contact digital signals from field devices such as emergency stop pushbuttons, pressure switches, and level switches, and transmits their state safely to the SLS 1508 logic solver for safety logic execution.
Detailed content
Technical Specifications
Manufacturer: Emerson Automation Solutions
Product Family: DeltaV SIS / SLS 1508 Logic Solver platform; DeltaV CHARMs I/O
Product Type: LS-CHARM Safety Digital Input Module
Channel Count: 16 isolated digital input channels
Input Type: Dry contact or wet contact (digital input)
Nominal Input Voltage: 24 V DC
Electrical Isolation: Channel-to-channel and channel-to-bus isolation
Safety Rating: SIL 3 per IEC 61508; TUV certified
Mounting: DIN-rail mounting on the CHARMs I/O carrier
Communication: DeltaV CHARM I/S card bus to the SLS 1508 logic solver
Hot-Swap: Supported, allowing module replacement under power without process shutdown
Operating Temperature Range: minus 40 to plus 85 degrees Celsius
Protection Rating: IP66 / NEMA 4X
Certifications: IEC 61508, TUV
Material Composition
Housing of industrial thermoplastic with flame-retardant rating; internal printed circuit boards with conformal coating for environmental protection; gold-plated connector contacts for reliable signal transmission; isolation transformers and opto-couplers providing channel-to-channel galvanic isolation.
Structural Features
Compact module housing that plugs onto the CHARMs I/O terminal block carrier. Each of the 16 channels includes independent isolation, signal conditioning, and diagnostic circuitry. The module carries no user-serviceable parts; configuration is performed in software through DeltaV Explorer or the DeltaV system engineering environment. LED indicators per channel show input status and fault state.
Functional Features
SIL 3 / TUV certified design delivers high diagnostic coverage for safety-critical applications, detecting internal faults, wiring faults, and channel failures. Channel-to-channel isolation eliminates ground loops and prevents cross-talk between field circuits, protecting the logic solver from voltage surges and electromagnetic interference. Emerson CHARM Electronic Marshalling allows the input signal type to be defined in software rather than through fixed physical wiring, reducing engineering effort and wiring errors and simplifying late project changes. The 16-channel density minimizes control cabinet footprint. Hot-swap support allows replacement of a failed module during operation without forcing a process shutdown. IP66 / NEMA 4X environmental protection supports field mounting in demanding applications.
Working Principle
Each field contact (dry or wet) is connected to a dedicated input channel. The channel circuitry applies wetting current (for dry contacts) or senses the applied 24 V DC signal (for wet contacts), performs debounce and filtering, and passes the state across galvanic isolation to the safety logic side. Continuous diagnostics monitor for open wire, short circuit, and internal circuit faults. Validated state and fault data are transmitted over the CHARM I/S bus to the SLS 1508 logic solver, where the safety logic (such as emergency shutdown voting) is executed.
Applications
Emergency shutdown (ESD) systems in oil and gas production and refining. Burner management systems (BMS) on offshore platforms, refineries, and gas processing plants. Fire and gas (F&G) detection input acquisition. High-integrity pressure, level, and temperature switch inputs on chemical reactors and storage tanks. Safety interlock inputs in power plants and onshore processing facilities requiring SIL 3 performance.
Installation Requirements
Mount the module on a DeltaV CHARMs I/O carrier on a standard DIN rail within the control cabinet or field junction box. Land the field wiring (16 digital inputs) on the CHARM terminal block following the DeltaV wiring diagrams, respecting dry-contact or wet-contact wiring conventions. Insert the SS4310T01 CHARM module onto the carrier until it latches. Configure each channel (dry contact, wet contact, debounce time, fault behavior) through the DeltaV engineering environment and download the configuration to the SLS 1508 logic solver. Verify SIL 3 loop validation checks (end-to-end response time, fault reaction) during commissioning.