B&R X20TB5E

Product Introduction:
The B&R X20TB5E is a grounding terminal block for the B&R X20 I/O system. It provides dedicated protective earth (PE) connection points for the X20 system, ensuring proper grounding of all connected I/O modules and field devices. The module features 5 grounding terminals rated for 16 A / 250 V, with a green-yellow color coding for immediate identification as a protective earth connection.

Detailed content

Technical Specifications:

  • Number of Terminals: 5
  • Terminal Type: Protective Earth (PE) / Grounding
  • Rated Current per Terminal: 16 A
  • Rated Voltage: 250 V AC / DC
  • Wire Cross Section0.5 mm² to 4 mm² (solid or stranded with ferrule)
  • Screw Torque: 0.8 Nm (recommended)
  • Wire Stripping Length10 mm
  • Isolation Voltage500 V DC (between terminals)
  • Color Coding: Green-yellow (per IEC 60446 / EN 60204)
  • Pollution Degree: 2 (per IEC 60664)
  • Operating Temperature0°C to +55°C
  • Storage Temperature-25°C to +70°C
  • Dimensions (W x H x D): 44 mm x 90 mm x 115 mm
  • WeightApprox. 0.1 kg
  • MountingDIN rail TS 35 (EN 60715)

Functional Features:

  • 5 dedicated PE (protective earth) terminals
  • Green-yellow color identification for immediate PE recognition (per safety standards)
  • Screw-clamp connection with tin-plated copper contacts
  • DIN rail mounting with snap-in clip
  • Label strip for terminal identification
  • Bridge connection capability to daisy-chain PE across multiple modules

Performance Parameters:

  • Contact Resistance< 3 mΩ (initial)
  • Contact Resistance (after life test)< 5 mΩ
  • Mechanical Life> 100 operations (screw/unscrew cycles)
  • Electrical Life> 10,000 operations (at rated load)
  • Vibration Resistance5 g (per IEC 60068-2-6)
  • Shock Resistance: 15 g (per IEC 60068-2-27)

Material Composition:

  • HousingFlame-retardant PA66 (polyamide 6.6) with glass fiber reinforcement, UL 94 V-0 rated, green-yellow color
  • Terminal ScrewsZinc-plated steel, corrosion-resistant
  • Terminal ContactsTin-plated copper alloy (CuSn6)
  • Label Strip: Polycarbonate (PC), green-yellow tinted
  • DIN Rail Clip: Spring steel, tin-plated

Structural Features:

  • Standard X20 module width44 mm
  • Front-facing X20 bus connector
  • 5 screw terminals on the front face, green-yellow housing
  • Full-width label strip (green-yellow)
  • Snap-in DIN rail mounting with locking clip

Working Principle:
The X20TB5E provides a dedicated low-impedance path to protective earth for the entire X20 system. All field devices and I/O modules are connected to this terminal block, and the PE conductor is routed to the main protective earth bar of the machine or cabinet. The screw-clamp terminals ensure a reliable, low-resistance connection (≤3 mΩ) that meets IEC 61131-2 and EN 60204-1 requirements for protective earthing. The green-yellow color coding ensures that this terminal is never mistakenly used for signal wiring.

Advantages & Highlights:

  • Dedicated PE connection — eliminates risk of accidental signal/earth mixing
  • Green-yellow color coding — compliant with IEC 60446, immediately recognizable
  • 5 terminals allow daisy-chaining of PE across multiple X20 modules
  • 16 A rating handles fault current safely
  • Low contact resistance (<3 mΩ) ensures effective fault clearing
  • Zero active components — maintenance-free

Applicable Industries:

  • All industries using B&R X20 systems (mandatory for CE/UL compliance)
  • Machine building
  • Packaging machinery
  • CNC machines
  • Printing presses
  • Any application requiring IEC 60204-1 compliance

Installation Requirements:

  • Mount on DIN rail TS 35 (EN 60715) — typically placed at one end of the X20 rack
  • Connect to X20 bus via rear bus connector
  • Connect the main PE conductor (green-yellow, min. 2.5 mm² for X20 systems) to one of the 5 terminals
  • Daisy-chain PE to other X20TB5E modules or directly to I/O module PE terminals
  • Use wire ferrules for stranded conductors
  • Strip wire to 10 mm, torque screws to 0.8 Nm

Usage Precautions:

  • Use ONLY for protective earth (PE) connections — never for signal or power wiring
  • Do not connect neutral (N) to PE at this terminal (N-PE bond must be at main supply only)
  • Verify PE continuity with a multimeter after installation (resistance < 1 Ω to main earth bar)
  • Do not exceed 16 A per terminal
  • Always use ferrules on stranded wire
  • Do not overtighten screws (max 0.8 Nm)