B&R X20TB5E
Product Introduction:
The B&R X20TB5E is a grounding terminal block for the B&R X20 I/O system. It provides dedicated protective earth (PE) connection points for the X20 system, ensuring proper grounding of all connected I/O modules and field devices. The module features 5 grounding terminals rated for 16 A / 250 V, with a green-yellow color coding for immediate identification as a protective earth connection.
Detailed content
Technical Specifications:
- Number of Terminals: 5
- Terminal Type: Protective Earth (PE) / Grounding
- Rated Current per Terminal: 16 A
- Rated Voltage: 250 V AC / DC
- Wire Cross Section: 0.5 mm² to 4 mm² (solid or stranded with ferrule)
- Screw Torque: 0.8 Nm (recommended)
- Wire Stripping Length: 10 mm
- Isolation Voltage: 500 V DC (between terminals)
- Color Coding: Green-yellow (per IEC 60446 / EN 60204)
- Pollution Degree: 2 (per IEC 60664)
- Operating Temperature: 0°C to +55°C
- Storage Temperature: -25°C to +70°C
- Dimensions (W x H x D): 44 mm x 90 mm x 115 mm
- Weight: Approx. 0.1 kg
- Mounting: DIN rail TS 35 (EN 60715)
Functional Features:
- 5 dedicated PE (protective earth) terminals
- Green-yellow color identification for immediate PE recognition (per safety standards)
- Screw-clamp connection with tin-plated copper contacts
- DIN rail mounting with snap-in clip
- Label strip for terminal identification
- Bridge connection capability to daisy-chain PE across multiple modules
Performance Parameters:
- Contact Resistance: < 3 mΩ (initial)
- Contact Resistance (after life test): < 5 mΩ
- Mechanical Life: > 100 operations (screw/unscrew cycles)
- Electrical Life: > 10,000 operations (at rated load)
- Vibration Resistance: 5 g (per IEC 60068-2-6)
- Shock Resistance: 15 g (per IEC 60068-2-27)
Material Composition:
- Housing: Flame-retardant PA66 (polyamide 6.6) with glass fiber reinforcement, UL 94 V-0 rated, green-yellow color
- Terminal Screws: Zinc-plated steel, corrosion-resistant
- Terminal Contacts: Tin-plated copper alloy (CuSn6)
- Label Strip: Polycarbonate (PC), green-yellow tinted
- DIN Rail Clip: Spring steel, tin-plated
Structural Features:
- Standard X20 module width: 44 mm
- Front-facing X20 bus connector
- 5 screw terminals on the front face, green-yellow housing
- Full-width label strip (green-yellow)
- Snap-in DIN rail mounting with locking clip
Working Principle:
The X20TB5E provides a dedicated low-impedance path to protective earth for the entire X20 system. All field devices and I/O modules are connected to this terminal block, and the PE conductor is routed to the main protective earth bar of the machine or cabinet. The screw-clamp terminals ensure a reliable, low-resistance connection (≤3 mΩ) that meets IEC 61131-2 and EN 60204-1 requirements for protective earthing. The green-yellow color coding ensures that this terminal is never mistakenly used for signal wiring.
Advantages & Highlights:
- Dedicated PE connection — eliminates risk of accidental signal/earth mixing
- Green-yellow color coding — compliant with IEC 60446, immediately recognizable
- 5 terminals allow daisy-chaining of PE across multiple X20 modules
- 16 A rating handles fault current safely
- Low contact resistance (<3 mΩ) ensures effective fault clearing
- Zero active components — maintenance-free
Applicable Industries:
- All industries using B&R X20 systems (mandatory for CE/UL compliance)
- Machine building
- Packaging machinery
- CNC machines
- Printing presses
- Any application requiring IEC 60204-1 compliance
Installation Requirements:
- Mount on DIN rail TS 35 (EN 60715) — typically placed at one end of the X20 rack
- Connect to X20 bus via rear bus connector
- Connect the main PE conductor (green-yellow, min. 2.5 mm² for X20 systems) to one of the 5 terminals
- Daisy-chain PE to other X20TB5E modules or directly to I/O module PE terminals
- Use wire ferrules for stranded conductors
- Strip wire to 10 mm, torque screws to 0.8 Nm
Usage Precautions:
- Use ONLY for protective earth (PE) connections — never for signal or power wiring
- Do not connect neutral (N) to PE at this terminal (N-PE bond must be at main supply only)
- Verify PE continuity with a multimeter after installation (resistance < 1 Ω to main earth bar)
- Do not exceed 16 A per terminal
- Always use ferrules on stranded wire
- Do not overtighten screws (max 0.8 Nm)