Product Series: B&R X20 I/O System (X20CM Series)

Product Introduction: The X20CM0985 is a single-channel CANopen communication module for the B&R X20 distributed I/O system. It enables the X20 I/O stations to communicate over a CANopen network (DS301, DS302, DS305 compliant), supporting device profile and SDO/PDO data exchange with CANopen masters.

Detailed content

Technical Specifications:

  • Communication ProtocolCANopen (CiA DS301, DS302, DS305, DS406)
  • CAN StandardCAN 2.0B (ISO 11898-1)
  • Number of Channels: 1 × CAN channel
  • Baud Rate: 10 kbps to 1 Mbps (configurable)
  • Connector: SUB-D 9-pin (male)
  • Supply Voltage: 24V DC via X20 bus connector
  • Power Consumption: Approx. 1.5 W
  • IsolationGalvanic isolation between CAN bus and X20 bus (500 V AC)
  • Protection RatingIP20

Functional Features:

  • Full CANopen device profile support (DS406)
  • SDO (Service Data Object) server and client
  • PDO (Process Data Object) mapping: up to 4 TPDO + 4 RPDO
  • Emergency message (EMCY) support (CiA 301)
  • Node guarding / Heartbeat support
  • LED indicators: Power (green), CAN Bus (green), Error (red)
  • Diagnostic counters: TX error, RX error, bus-off counter

Structural Features:

  • Form Factor: 45 mm width, X20 standard
  • MountingDIN rail 35 mm / direct screw
  • ConnectorX20 bus (top) + SUB-D 9 (front)
  • Housing MaterialPolycarbonate (PC), UL94 V-0
  • Dimensions (W × H × D): 45 mm × 90 mm × 75 mm (approx.)
  • Weight: Approx. 125 g

Operating Conditions:

  • Operating Temperature-25°C to +70°C
  • Storage Temperature-40°C to +85°C
  • Relative Humidity5% to 95% (non-condensing)

Applicable Industries:

  • Mobile hydraulics (CANopen J1939 bridge)
  • Agricultural machinery
  • Construction equipment
  • Marine automation
  • Building automation (HVAC controllers)
  • Medical equipment

Installation Requirements:

  • Mount on DIN rail adjacent to X20 CPU/I/O modules
  • Connect CAN_H and CAN_L using shielded twisted-pair cable
  • Terminate both ends of CAN bus with 120 Ω resistor
  • Maximum bus length: 40 m at 1 Mbps; 1000 m at 10 kbps
  • Ensure common ground reference between nodes (optional, depends on isolation)

Usage Precautions:

  • Always terminate CAN bus at both physical ends with 120 Ω
  • Do not exceed 1 Mbps baud rate
  • Use shielded twisted-pair cable, ground shield at one end
  • Do not connect CAN_H and CAN_L to power supply

Advantages & Highlights:

  • Full CiA 406 device profile — plug-and-play with any CANopen master
  • Galvanic isolation protects X20 bus from CAN bus transients
  • Wide baud rate range (10 kbps–1 Mbps) covers all CANopen applications
  • Compact X20 form factor — no separate gateway required