Digital guide

You are here:

B&R X20BB80

Product Series: B&R X20 BB Series (Digital Input)

Product Overview:
The X20BB80 is an 8-channel digital input module for 24 V DC signals in the B&R X20 I/O system. It provides group galvanic isolation and is designed for applications requiring a moderate number of digital inputs in a compact form factor.

Detailed content

Key Technical Specifications:

Parameter Value
Number of Channels 8
Input Type Digital (24 V DC)
Input Voltage Range 10 V DC to 30 V DC (logic “1”)
Input Current (Logic “1”) Typical 4 mA
Input Current (Logic “0”) < 1 mA
Isolation Group-to-group: 500 V DC
Response Time (ON → OFF) ≤ 0.2 ms (typ.)
Response Time (OFF → ON) ≤ 0.2 ms (typ.)
Supply Voltage 24 V DC (±20%)
Power Consumption ≤ 1.2 W
Operating Temperature -25°C to +70°C
Protection Class IP20 (front), IP65 (with housing)
Dimensions (W x H x D) 90 mm x 120 mm x 74.5 mm
Weight Approximately 180 g
Connection Screw terminal, 2.5 mm²
Diagnostics Basic input status only — no wire-break diagnostic

Functional Features:

  • 8 independent digital inputs
  • Source (PNP) and sink (NPN) compatibility
  • Group isolation between input banks
  • Fast 0.2 ms response time
  • 8 status LEDs for visual verification

Working Principle:
Each input channel uses an optocoupler for galvanic isolation. The 24 V DC input signal drives the optocoupler LED, and the phototransistor output is processed by the module’s internal logic. Data is transmitted to the PLC via the X20 bus. The 8 channels are divided into groups with 500 V DC isolation between groups.

Material Composition:

  • HousingGlass-fiber reinforced polyamide (PA66-GF30), halogen-free
  • TerminalsTin-plated copper alloy
  • PCB: FR-4, conformally coated

Structural Characteristics:

  • DIN rail mounting (TS 35, EN 60715)
  • Spring-loaded terminal connections
  • 8 status LEDs
  • Module width15 mm (X20 standard)

Advantages & Highlights:

  • Low power consumption of ≤ 1.2 W
  • Compact size for space-constrained cabinets
  • Fast response suitable for high-speed applications
  • Wide input voltage range (10–30 V DC) for noise immunity
  • Cost-effective solution for 8-channel applications

Applicable Industries:

  • Small machine automation
  • Conveyor systems
  • Gate and barrier control
  • Light curtain interfacing
  • Valve position monitoring
  • General purpose OEM machinery

Installation Requirements:

  • Mount on DIN rail TS 35 (EN 60715)
  • Connect 24 V DC sensors — PNP or NPN compatible
  • Maintain 10 mm spacing between modules
  • Terminate unused inputs to prevent floating signals

Usage Precautions:

  • No wire-break diagnostic — use X20BB81 if diagnostics are required
  • Do not exceed 30 V DC on any input
  • Ensure correct PNP/NPN wiring based on sensor type
  • Store at -40°C to +85°C