B&R 5C5001.11
Material Composition:
28 strands of 0.26 mm tinned copper per conductor (Class 5 flexibility) ensure easy routing in tight spaces. PVC insulation rated to 70°C continuous provides basic electrical isolation. PVC outer sheath offers moderate mechanical protection and chemical resistance — suitable for control cabinet wiring, sensor power feeds, and low-power actuator connections.
Detailed content
Core Technical Specifications:
| Parameter | Value |
|---|---|
| Conductor Cross-Section | 1.5 mm² |
| Number of Conductors | 4 (3 phases U/V/W + PE) |
| Voltage Rating (U0/U) | 300/500 V (AC) / 750 V (DC) |
| Cable Standard | H05VV-F per VDE 0250 / IEC 60227-5 |
| Conductor Material | Fine-stranded copper, Class 5 per IEC 60228 (28 strands of 0.26 mm) |
| Insulation Material | PVC (Polyvinyl Chloride), 70°C rated |
| Outer Sheath Material | PVC (black, RAL 9005) |
| Color Coding | Brown (U), Black (V), Gray (W), Green/Yellow (PE) |
| Cable Length (Standard) | 1 meter (also available: 5 m, 10 m, 25 m rolls) |
| Minimum Bend Radius (Fixed) | 4 × cable OD ≈ 16 mm |
| Minimum Bend Radius (Flexible) | 6 × cable OD ≈ 24 mm |
| Current Rating (Method A, air) | 15.5 A (3-core, PVC, IEC 60364-5-52) |
| Current Rating (Method B, on surface) | 19.5 A (3-core, PVC, IEC 60364-5-52) |
| Ambient Temperature (Fixed) | -15°C to +70°C |
| Ambient Temperature (Flexible) | -5°C to +70°C |
| Fire Performance | IEC 60332-1-2 (flame retardant) |
| Certifications | CE, VDE, UL 2556 (varies by length) |
Functional Features:
This is a general-purpose flexible cable — it is NOT designed for servo motor power connections (which require double-shielded PUR cables like 4C2210.01-510). It is suitable for 24 V DC and 230 V AC control circuits up to 500 V. The fine-stranded conductors enable repeated flexing in cable carriers without conductor fatigue.
Applicable Industries:
Control cabinet internal wiring, sensor/actuator power distribution, relay coil connections, solenoid valve power feeds, indicator light circuits, general machine building.
Installation Requirements:
Route in cable tray or conduit. Maintain minimum bend radius (16 mm fixed / 24 mm flexible). Separate from 400 V+ power cables by minimum 50 mm. Use cable glands (PG7–PG11) for entry into enclosures. Label both ends per wiring diagram / IEC 81346. Torque cable gland nut to 0.5 Nm (PG7) to 2.5 Nm (PG16).
Critical Usage Directives:
DO NOT use for ACOPOS servo motor connections — servo drives require double-shielded PUR cables (4C series) to meet EMC requirements. Verify voltage rating matches circuit (max 500 V AC). Do not use in explosion-hazard areas (ATEX Zone 0/1/2) without additional protection. Replace if PVC jacket shows cracking, discoloration, or hardness changes (indicates aging). Maximum continuous conductor temperature: 70°C.