B&R 3IF050.6
Product Type: 8-Channel Analog Input Module
Product Description:
The B&R 3IF050.6 is an 8-channel analog input module from the B&R X20 distributed I/O system. It accepts voltage and current signals from field sensors and transmitters and converts them to digital values for the PLC. Each channel is electrically isolated.
Detailed content
Technical Specifications:
- Number of Channels: 8 analog inputs (single-ended)
- Resolution: 12-bit A/D converter
- Input Ranges (selectable per channel group):
- Voltage: ±10 V, 0 to +10 V, ±5 V, 0 to +5 V
- Current: 0 to 20 mA, 4 to 20 mA, ±20 mA
- Sampling Rate: Up to 10 kHz per channel (aggregate), 1 kHz per channel (simultaneous sampling)
- Isolation: Channel-to-channel isolation, 500 V DC; field-side to logic-side isolation, 500 V DC
- Accuracy: ±0.1% of full scale (typical at 25 °C)
- Common Mode Rejection Ratio (CMRR): ≥ 80 dB
- Bus System: X20 System Bus (SERCOS-compatible backbone)
- Power Supply: 24 V DC via X20 bus connector
- Power Consumption: ≤ 1.5 W
- Operating Temperature: -25 °C to +70 °C
- Protection Rating: IP20 (when mounted in X20 base/coupler)
- Dimensions (W × H × D): 25 mm × 90 mm × 75 mm
- Weight: Approximately 100 g
Functional Features:
- Configurable per-channel range via Automation Studio
- Software filtering (moving average, low-pass) configurable per channel
- Diagnostic functions: overrange, underrange, wire-break detection
- Hot-swappable when used with X20 base units
- LED status indicators per channel group
Structural Characteristics:
- Plastic housing (PA66 GF30, UL94 V-0 rated)
- Spring-loaded terminal connectors (push-in technology) for fast wiring
- DIN rail TS 35 mounting or direct mounting on X20 base
- LED indicators: Power (green), Fault (red), Channel status (yellow)
Material Composition:
- Housing: Glass-fiber reinforced polyamide (PA66-GF30)
- Terminal blocks: Phosphor bronze, tin-plated
- PCB: FR-4, conformally coated
- Connectors: Gold-plated contact pins
Applicable Industries:
- Process automation (chemical, pharmaceutical)
- HVAC and building management
- Water/wastewater treatment
- Food and beverage production
- Energy management systems
Installation Requirements:
- Mount on X20 Base (3EX280.60-1 or equivalent) or X20 Coupler
- Shielded cables required for analog signals; shield grounded at one end only
- Maximum cable length: 10 m (unshielded), 100 m (shielded)
- Do not mix signal types on same module — use separate modules for thermocouples/RTDs