Digital guide

You are here:

B&R 3AO360.60-1

Model Series: X20 System (AO = Analog Module — Output)

Product Overview:
The 3AO360.60-1 is a 2-channel analog output module from B&R’s X20 I/O system. It generates analog control signals (current or voltage) to drive field actuators such as control valves, variable frequency drives (VFDs), and proportional controllers. The module features 12-bit resolution and supports both 4–20 mA and 0–10 V output ranges.

Detailed content

Technical Specifications:

  • Module Type: Analog Output (AO)
  • Number of Channels: 2 channels
  • Output Signal Types: 4–20 mA (2-wire, loop-powered) OR 0–10 V DC
  • Resolution: 12 bit (4096 steps)
  • Output Accuracy: ±0.2% of full scale (at 25 °C)
  • Output Update Rate: 1 ms (both channels simultaneous update)
  • Output Current (4–20 mA mode): 0 mA to 20 mA (max loop voltage: 24 V DC)
  • Output Voltage (0–10 V mode): 0 V to 10 V DC (max load: 2 kΩ minimum)
  • Isolation Voltage: 500 V DC (channel-to-channel, channel-to-bus)
  • Communication Interface: X20 Link (100 Mbps Ethernet)
  • Bus Connection: RJ45 connector (X20 bus daisy-chain)
  • Power Supply: 24 V DC via X20 bus
  • Power Consumption: Approximately 2.0 W (typical)
  • Protection Rating: IP20
  • Operating Temperature: 0 °C to +55 °C
  • Storage Temperature: -25 °C to +70 °C
  • Dimensions (W × H × D): Approximately 45 mm × 90 mm × 75 mm
  • Weight: Approximately 0.12 kg
  • Mounting: DIN rail TS 35, 7.5 mm width per module

Functional Features:

  • 2 independent analog output channels
  • Configurable per-channel: 4–20 mA or 0–10 V
  • 12-bit resolution with simultaneous update
  • Galvanic isolation on all channels
  • LED status indicators per channel
  • Diagnostic data (output status, fault) via Automation Studio
  • Hot-swap capable on X20 bus

Applicable Industries:
Process control, HVAC, water treatment, oil and gas, chemical processing, building automation, pump and valve control.

Installation Requirements:

  • Mount on DIN rail TS 35 (7.5 mm module width)
  • Connect to X20 bus via RJ45 daisy-chain
  • 24 V DC power via X20 bus — no external power required
  • For 4–20 mA: connect actuator in series with module output (loop-powered)
  • For 0–10 V: connect to high-impedance input of actuator/drive
  • Use shielded twisted-pair cable for all analog outputs
  • Max cable length: 100 m (shielded)

Usage Notes:

  • In 4–20 mA mode: total loop voltage (module + actuator + wiring drop) must not exceed 24 V DC
  • In 0–10 V mode: load impedance must be ≥ 2 kΩ
  • Do not short-circuit output terminals
  • Calibrate zero and span via Automation Studio for each channel
  • Single-point shield grounding at controller end