Digital guide

You are here:

B&R 2BP201.40-010

Model Series: 2BP (Power Supply for APC 200)

Product Overview:
The 2BP201.40-010 is a 24 V DC switch-mode power supply (SMPS) specifically designed for B&R’s Automation PC 200 (APC 200) series. It provides regulated 24 V DC output with high efficiency and wide input voltage range, enabling operation from global AC mains voltages.

Detailed content

Technical Specifications:

  • Output Voltage: 24 V DC (adjustable ±5%)
  • Output Current: 2.1 A (continuous)
  • Output Power: 50 W (maximum)
  • Input Voltage Range: 100 V AC to 240 V AC (single-phase, 50/60 Hz)
  • Input Frequency: 50 Hz / 60 Hz (auto-sensing)
  • Efficiency: Greater than 85% (at full load)
  • Output Ripple: Less than 100 mV peak-to-peak
  • Output Noise: Less than 50 mV RMS
  • Protection Features: Short-circuit protection, overcurrent protection, overvoltage protection, overtemperature protection
  • Protection Rating: IP20
  • Operating Temperature: 0 °C to +50 °C (derating above +40 °C)
  • Storage Temperature: -25 °C to +70 °C
  • MTBF: Greater than 100,000 hours (at 25 °C)
  • Dimensions (W × H × D): Approximately 50 mm × 90 mm × 60 mm
  • Weight: Approximately 0.25 kg
  • Mounting: DIN rail TS 35
  • Safety Certifications: CE, UL, cUL, CCC

Functional Features:

  • Universal AC input (100–240 V AC) for worldwide deployment
  • High efficiency reduces heat generation
  • Comprehensive protection circuitry for system safety
  • DIN rail mounting for cabinet installation
  • Low EMC emissions per EN 61000-6-4

Applicable Industries:
Machine building, panel building, OEM equipment, food and beverage, pharmaceutical, general industrial automation.

Installation Requirements:

  • Mount on DIN rail TS 35
  • Connect AC mains via terminal block (L, N, PE)
  • Connect DC output via terminal block (+V, -V)
  • Ensure adequate ventilation (minimum 10 mm clearance on all sides)
  • Use wire cross-section per current rating: minimum 1.5 mm² for output

Usage Notes:

  • Do not block ventilation openings
  • Output voltage adjustment via internal potentiometer (±5% range)
  • Derate output current by 1% per °C above +40 °C ambient
  • Ensure proper PE (protective earth) connection

You may also like