B&R 2BP201.40-010
Model Series: 2BP (Power Supply for APC 200)
Product Overview:
The 2BP201.40-010 is a 24 V DC switch-mode power supply (SMPS) specifically designed for B&R’s Automation PC 200 (APC 200) series. It provides regulated 24 V DC output with high efficiency and wide input voltage range, enabling operation from global AC mains voltages.
Detailed content
Technical Specifications:
- Output Voltage: 24 V DC (adjustable ±5%)
- Output Current: 2.1 A (continuous)
- Output Power: 50 W (maximum)
- Input Voltage Range: 100 V AC to 240 V AC (single-phase, 50/60 Hz)
- Input Frequency: 50 Hz / 60 Hz (auto-sensing)
- Efficiency: Greater than 85% (at full load)
- Output Ripple: Less than 100 mV peak-to-peak
- Output Noise: Less than 50 mV RMS
- Protection Features: Short-circuit protection, overcurrent protection, overvoltage protection, overtemperature protection
- Protection Rating: IP20
- Operating Temperature: 0 °C to +50 °C (derating above +40 °C)
- Storage Temperature: -25 °C to +70 °C
- MTBF: Greater than 100,000 hours (at 25 °C)
- Dimensions (W × H × D): Approximately 50 mm × 90 mm × 60 mm
- Weight: Approximately 0.25 kg
- Mounting: DIN rail TS 35
- Safety Certifications: CE, UL, cUL, CCC
Functional Features:
- Universal AC input (100–240 V AC) for worldwide deployment
- High efficiency reduces heat generation
- Comprehensive protection circuitry for system safety
- DIN rail mounting for cabinet installation
- Low EMC emissions per EN 61000-6-4
Applicable Industries:
Machine building, panel building, OEM equipment, food and beverage, pharmaceutical, general industrial automation.
Installation Requirements:
- Mount on DIN rail TS 35
- Connect AC mains via terminal block (L, N, PE)
- Connect DC output via terminal block (+V, -V)
- Ensure adequate ventilation (minimum 10 mm clearance on all sides)
- Use wire cross-section per current rating: minimum 1.5 mm² for output
Usage Notes:
- Do not block ventilation openings
- Output voltage adjustment via internal potentiometer (±5% range)
- Derate output current by 1% per °C above +40 °C ambient