AEG AS-9584-000
Product Type: 8-Channel Analog Input/Output Module
Product Overview:
The AEG AS-9584-000 is an 8-channel analog I/O module providing 4 analog inputs and 4 analog outputs in a single compact unit. It is designed for process control applications requiring precise analog signal acquisition and generation.
Detailed content
Technical Specifications:
- Analog Inputs: 4 channels, 0–10 V DC or 4–20 mA, 16-bit resolution
- Analog Outputs: 4 channels, 0–10 V DC or 4–20 mA, 16-bit resolution
- Input Impedance (Voltage): > 1 MΩ
- Input Impedance (Current): 250 Ω (burden for 4–20 mA)
- Output Load (Voltage): > 10 kΩ minimum
- Output Load (Current): < 500 Ω maximum (for 4–20 mA)
- Accuracy: ± 0.2% of full scale
- Isolation Voltage: 1500 V DC (input-to-output, channel-to-channel, channel-to-bus)
- Sampling Rate: 1 kHz per channel (all channels simultaneous)
- Supply Voltage: 24 V DC ± 15%
- Power Consumption: Maximum 2.5 W
- Operating Temperature: -20°C to +60°C
- Protection Rating: IP20
- Dimensions: 90 mm x 70 mm x 45 mm
- Weight: 170 g
Material Composition:
- Housing: Flame-retardant polycarbonate, light grey, UL94 V-0
- ADC: Texas Instruments ADS8688 (16-bit, 8-channel, simultaneous sampling)
- DAC: Texas Instruments DAC8568 (16-bit, quad, voltage/current output)
- Isolation: Analog Devices ADuM1401 (digital), Si864x (analog), 5 kV
- Terminals: Phoenix Contact, screw-type, 2.5 mm²
Structural Features:
- DIN rail mountable (35 mm)
- 4 LED indicators for input status, 4 LED indicators for output status
- DIP switches for input range (0–10 V / 4–20 mA) and output range
- Backplane bus connector for controller communication
- Spring-clamp terminals for fast wiring
Working Principle:
Analog inputs are simultaneously sampled by the ADS8688 ADC (16-bit, 1 kHz) via a multiplexed front-end with precision op-amp buffer (OPA2277). The digital data is transmitted over the backplane bus. Analog outputs are generated by the DAC8568 (16-bit quad DAC). For 4–20 mA output, a voltage-to-current converter (XTR116 or equivalent) converts the DAC voltage to a proportional current. All channels are optically isolated from the bus using Si864x isolators (5 kV).
Key Advantages:
- Simultaneous sampling (1 kHz) for all 4 input channels — no skew
- 16-bit resolution (± 0.2% FS) for high-precision applications
- Flexible configuration (0–10 V or 4–20 mA per channel via DIP switch)
- Fully isolated channels prevent cross-talk and ground loops
Applicable Industries:
Process control, water treatment, chemical dosing, HVAC, building automation, test & measurement.
Installation Requirements:
- Mount on 35 mm DIN rail
- Use shielded twisted-pair cable for 4–20 mA signals
- Set DIP switches for correct range before connecting sensors/actuators
- Ground cable shields at one end only
Usage Precautions:
- Do not apply voltage > 12 V DC to 0–10 V input range
- For 4–20 mA output, ensure load resistance does not exceed 500 Ω (for 24 V supply)
- Do not short-circuit 4–20 mA output (can damage DAC)
- Calibrate zero and span annually using precision calibrator