Digital guide

You are here:

AEG AS-9584-000

Product Type: 8-Channel Analog Input/Output Module

Product Overview:
The AEG AS-9584-000 is an 8-channel analog I/O module providing 4 analog inputs and 4 analog outputs in a single compact unit. It is designed for process control applications requiring precise analog signal acquisition and generation.

Detailed content

Technical Specifications:

  • Analog Inputs4 channels, 0–10 V DC or 4–20 mA, 16-bit resolution
  • Analog Outputs: 4 channels, 0–10 V DC or 4–20 mA, 16-bit resolution
  • Input Impedance (Voltage): > 1 MΩ
  • Input Impedance (Current): 250 Ω (burden for 4–20 mA)
  • Output Load (Voltage)> 10 kΩ minimum
  • Output Load (Current): < 500 Ω maximum (for 4–20 mA)
  • Accuracy: ± 0.2% of full scale
  • Isolation Voltage1500 V DC (input-to-output, channel-to-channel, channel-to-bus)
  • Sampling Rate1 kHz per channel (all channels simultaneous)
  • Supply Voltage: 24 V DC ± 15%
  • Power Consumption: Maximum 2.5 W
  • Operating Temperature: -20°C to +60°C
  • Protection RatingIP20
  • Dimensions: 90 mm x 70 mm x 45 mm
  • Weight: 170 g

Material Composition:

  • Housing: Flame-retardant polycarbonate, light grey, UL94 V-0
  • ADC: Texas Instruments ADS8688 (16-bit, 8-channel, simultaneous sampling)
  • DACTexas Instruments DAC8568 (16-bit, quad, voltage/current output)
  • IsolationAnalog Devices ADuM1401 (digital), Si864x (analog), 5 kV
  • Terminals: Phoenix Contact, screw-type, 2.5 mm²

Structural Features:

  • DIN rail mountable (35 mm)
  • 4 LED indicators for input status, 4 LED indicators for output status
  • DIP switches for input range (0–10 V / 4–20 mA) and output range
  • Backplane bus connector for controller communication
  • Spring-clamp terminals for fast wiring

Working Principle:
Analog inputs are simultaneously sampled by the ADS8688 ADC (16-bit, 1 kHz) via a multiplexed front-end with precision op-amp buffer (OPA2277). The digital data is transmitted over the backplane bus. Analog outputs are generated by the DAC8568 (16-bit quad DAC). For 4–20 mA output, a voltage-to-current converter (XTR116 or equivalent) converts the DAC voltage to a proportional current. All channels are optically isolated from the bus using Si864x isolators (5 kV).

Key Advantages:

  • Simultaneous sampling (1 kHz) for all 4 input channels — no skew
  • 16-bit resolution (± 0.2% FS) for high-precision applications
  • Flexible configuration (0–10 V or 4–20 mA per channel via DIP switch)
  • Fully isolated channels prevent cross-talk and ground loops

Applicable Industries:
Process control, water treatment, chemical dosing, HVAC, building automation, test & measurement.

Installation Requirements:

  • Mount on 35 mm DIN rail
  • Use shielded twisted-pair cable for 4–20 mA signals
  • Set DIP switches for correct range before connecting sensors/actuators
  • Ground cable shields at one end only

Usage Precautions:

  • Do not apply voltage > 12 V DC to 0–10 V input range
  • For 4–20 mA output, ensure load resistance does not exceed 500 Ω (for 24 V supply)
  • Do not short-circuit 4–20 mA output (can damage DAC)
  • Calibrate zero and span annually using precision calibrator