Product Name: AEG 7628-042.20059 Thermal Overload Relay

Product Series: 7628 Series Thermal Overload Relays

Product Type: Bimetallic Thermal Overload Relay (Motor Protection)

Current Range9 – 13 A (adjustable via dial)

Detailed content

Trip Class: Class 10A (standard); Class 20, Class 30 available

Number of Poles3 poles (3NO + 3NC auxiliary contacts)

Auxiliary Contact Rating: 6 A at 250 V AC (resistive load)

Control Supply Voltage: 220 – 240 V AC / 110 – 127 V AC (selectable)

Motor Rating (at 400 V, 50 Hz, AC-3)4 kW (3-phase)

Trip Time at 7.2× In≤ 20 seconds (Class 10A)

Trip Time at 7.2× In≤ 10 seconds (Class 20)

Reset ModeManual reset (push-button) / Automatic reset (selectable via jumper)

Mounting: DIN rail 35 mm / Direct screw mount

Protection Class: IP20 (front); IP40 (with cover)

Ambient Temperature: -25°C to +60°C

Standards ComplianceIEC 60947-4-1, EN 60947-4-1, UL 508, CSA C22.2 No. 14

Housing MaterialPolyamide 6.6 (self-extinguishing, UL94 V-0)

Dimensions: 45 mm × 85 mm × 65 mm (W × H × D)

Key Features:

  • Phase-failure protection (unbalanced current detection)
  • Ambient temperature compensation: -10°C to +40°C automatic adjustment
  • Test button for contact verification without motor current
  • Trip indicator flag (red) for visual fault identification

Applicable Industries: All 3-phase motor applications — pumps, compressors, conveyors, fans, mixers

Installation Requirements:

  • Connect in series with motor power circuit (L1, L2, L3)
  • Auxiliary NC contact (95-96) wired in series with contactor coil circuit
  • Tighten terminal screws to 0.8 Nm torque
  • Set current dial to motor full-load amperage (FLA)

Usage Notes:

  • After trip, allow 3 minutes cooling before reset (Class 10A)
  • Do not use for short-circuit protection — pair with fuse or MCB
  • Verify phase-loss function monthly via test button