Detailed content
Rated Voltage (Ue): 230/400 V AC
Breaking Capacity (Icu): 6 kA at 230 V AC
Breaking Capacity (Ics): 6 kA at 230 V AC (100% Icu)
Trip Curve: Curve C (trip range: 5×In to 10×In = 30 A to 60 A instantaneous)
Number of Poles: 1P (single pole)
Rated Frequency: 50/60 Hz
Mechanical Life: 20,000 operations
Electrical Life: 10,000 operations at rated current
Connection: Screw terminal, 1–25 mm² wire capacity
Mounting: 35 mm DIN rail (EN 60715, TH35)
Protection Class: IP20 (front); IP40 with terminal cover
Operating Temperature: -25°C to +70°C
Standards: IEC 60898-1, EN 60898-1, UL 489, CSA C22.2 No. 5
Housing Material: Polycarbonate (UL94 V-0), self-extinguishing
Dimensions (W × H × D): 17.5 mm × 85 mm × 68 mm
Weight: 65 g
Key Features:
- Curve C suitable for general-purpose and motor circuits with moderate inrush
- Visual trip indicator: white = ON, red = TRIPPED
- Terminal tightening torque: 2.5 Nm maximum
- Coordinated selectivity with upstream 6 kA breakers
Applicable Industries: Residential, commercial, light industrial distribution boards, machine control panels
Installation Requirements:
- Mount on 35 mm DIN rail, snap-in or screw-fix
- Strip wire insulation 10 mm, insert fully into terminal
- Ensure tight connection — loose terminals cause overheating
- Maintain ≥ 3 mm spacing between adjacent breakers for heat dissipation
Usage Notes:
- Reset by switching handle to OFF then ON after fault clearance
- Do not use as isolator — use dedicated isolator switch upstream
- Replace after fault current exceeding Icu (breaker must be replaced, not reset)