AEG 140CRA21110

Product Name: AEG 140CRA21110 Molded Case Circuit Breaker (MCCB)

Product Series: 140CRA Series Molded Case Circuit Breakers

Product Type: 3-Pole MCCB with Electronic Trip Unit, Fixed Mounting

Rated Current (In): 100 A

Detailed content

Rated Voltage (Ue): 690 V AC (50/60 Hz)

Rated Insulation Voltage (Ui)690 V AC

Rated Impulse Withstand Voltage (Uimp)8 kV

Breaking Capacity (Icu)50 kA at 690 V AC (conditional, with upstream protection)

Breaking Capacity (Ics)35 kA at 690 V AC (100% of Icu)

Trip Unit Type: Electronic — Micrologic 5.2E (LSIG protection)

  • L (Long-time delay): Adjustable 0.4 – 1.0 × In (40 A – 100 A), trip time adjustable: 6 s – 30 s at 6×In
  • S (Short-time delay): Adjustable 1.5 – 10 × In (150 A – 1000 A), trip time: 0.1 s – 0.4 s
  • I (Instantaneous): Adjustable 1.5 – 10 × In (150 A – 1000 A), trip time: < 20 ms
  • G (Ground fault): Adjustable 0.2 – 1.0 × In (20 A – 100 A), trip time: 0.1 s – 0.4 s

Number of Poles3P (three-pole) + N (neutral, linked)

Rated Frequency50/60 Hz

Mechanical Life25,000 operations

Electrical Life: 15,000 operations at rated current

ConnectionFront-connected or rear-connected (screw terminal), 16 – 95 mm² wire capacity

MountingFixed mounting (bolt-on); draw-out version available separately

Protection ClassIP40 (front terminal cover); IP54 (with full enclosure)

Operating Temperature: -25°C to +70°C

StandardsIEC 60947-2, EN 60947-2, UL 489, CSA C22.2 No. 5, CE

Housing Material: Glass-fiber reinforced polyester (self-extinguishing, UL94 V-0)

Dimensions (W × H × D)105 mm × 225 mm × 115 mm

Weight4.8 kg

Key Features:

  • Electronic trip unit with LCD display showing real-time current, power, energy
  • Zone Selective Interlocking (ZSI) capability for selective coordination
  • Event logging: stores last 32 trip events with timestamp and fault current
  • Communication: Modbus RTU (RS-485) for SCADA integration
  • Rotary handle: ON / OFF / TRIP — red flag indicator for fault status

Applicable Industries: Main incoming breaker, feeder protection, motor control centers (MCC), generator protection, transformer secondary protection, large commercial buildings, industrial plants

Installation Requirements:

  • Torque terminal screws to 12 Nm (for 95 mm² cable)
  • Bus bar connection: use AEG copper bus bars rated ≥ 100 A
  • Ensure minimum 200 mm cable bend radius at terminals
  • For draw-out version: engage racking mechanism fully — do not rack under load

Usage Notes:

  • Perform insulation resistance test (≥ 1 MΩ at 500 V DC) annually
  • Calibrate trip unit settings using AEG testing set or commissioning software
  • After fault trip, read event log via Modbus or front-panel buttons before resetting
  • Coordinate upstream/downstream breakers using selectivity tables (I²t coordination)
  • Replace breaker after Icu-level fault — internal arc chutes are single-use