Rated Voltage (Ue): 690 V AC (50/60 Hz)
Rated Insulation Voltage (Ui): 690 V AC
Rated Impulse Withstand Voltage (Uimp): 8 kV
Breaking Capacity (Icu): 50 kA at 690 V AC (conditional, with upstream protection)
Breaking Capacity (Ics): 35 kA at 690 V AC (100% of Icu)
Trip Unit Type: Electronic — Micrologic 5.2E (LSIG protection)
- L (Long-time delay): Adjustable 0.4 – 1.0 × In (40 A – 100 A), trip time adjustable: 6 s – 30 s at 6×In
- S (Short-time delay): Adjustable 1.5 – 10 × In (150 A – 1000 A), trip time: 0.1 s – 0.4 s
- I (Instantaneous): Adjustable 1.5 – 10 × In (150 A – 1000 A), trip time: < 20 ms
- G (Ground fault): Adjustable 0.2 – 1.0 × In (20 A – 100 A), trip time: 0.1 s – 0.4 s
Number of Poles: 3P (three-pole) + N (neutral, linked)
Rated Frequency: 50/60 Hz
Mechanical Life: 25,000 operations
Electrical Life: 15,000 operations at rated current
Connection: Front-connected or rear-connected (screw terminal), 16 – 95 mm² wire capacity
Mounting: Fixed mounting (bolt-on); draw-out version available separately
Protection Class: IP40 (front terminal cover); IP54 (with full enclosure)
Operating Temperature: -25°C to +70°C
Standards: IEC 60947-2, EN 60947-2, UL 489, CSA C22.2 No. 5, CE
Housing Material: Glass-fiber reinforced polyester (self-extinguishing, UL94 V-0)
Dimensions (W × H × D): 105 mm × 225 mm × 115 mm
Weight: 4.8 kg
Key Features:
- Electronic trip unit with LCD display showing real-time current, power, energy
- Zone Selective Interlocking (ZSI) capability for selective coordination
- Event logging: stores last 32 trip events with timestamp and fault current
- Communication: Modbus RTU (RS-485) for SCADA integration
- Rotary handle: ON / OFF / TRIP — red flag indicator for fault status
Applicable Industries: Main incoming breaker, feeder protection, motor control centers (MCC), generator protection, transformer secondary protection, large commercial buildings, industrial plants
Installation Requirements:
- Torque terminal screws to 12 Nm (for 95 mm² cable)
- Bus bar connection: use AEG copper bus bars rated ≥ 100 A
- Ensure minimum 200 mm cable bend radius at terminals
- For draw-out version: engage racking mechanism fully — do not rack under load
Usage Notes:
- Perform insulation resistance test (≥ 1 MΩ at 500 V DC) annually
- Calibrate trip unit settings using AEG testing set or commissioning software
- After fault trip, read event log via Modbus or front-panel buttons before resetting
- Coordinate upstream/downstream breakers using selectivity tables (I²t coordination)
- Replace breaker after Icu-level fault — internal arc chutes are single-use