  • Product Introduction: It is a power filter module designed for AEG industrial control equipment, which is used to filter out electromagnetic interference (EMI) and radio frequency interference (RFI) in the power supply line, protect the PLC, frequency converter and other precision equipment from the impact of grid noise, and ensure the stable and reliable operation of the equipment.
  • Technical Specifications:
    • Input Voltage: 220‑240 VAC, 50/60 Hz; Rated Current: 10 A.
    • Filtering Performance: It can suppress common‑mode and differential‑mode interference, and the attenuation of interference signals above 1 MHz is ≥40 dB.
    • Leakage Current: ≤1 mA; Response Time: ≤1 μs.

Detailed content

    • Protection Functions: Overcurrent protection and overvoltage protection, automatic shutdown when the current exceeds 12 A or the voltage exceeds 264 VAC.
    • Operating Temperature: -25°C to +70°C; Protection Rating: IP30; Dimensions: 100mm × 80mm × 40mm (W×H×D); Power Loss: ≤1 W.
  • Functional Features:
    • The dual‑stage filtering circuit design has a strong filtering effect and can adapt to the harsh power grid environment in the industrial field.
    • The metal shell has good shielding performance, which can prevent the filter itself from radiating interference signals outward.
    • It can be installed on the DIN rail, and the installation and disassembly are simple, which is convenient for system maintenance and replacement.
    • It complies with international EMC standards such as IEC 61000‑4‑5, and can meet the electromagnetic compatibility requirements of most industrial equipment.
    • The service life is long, and the average trouble‑free working time is more than 50,000 hours.
  • Application Scenarios: It is widely used in industrial control cabinets, such as the power input end of AEG Modicon series PLC, the power supply part of frequency converters, servo drivers, and precision sensors. It is especially suitable for occasions with serious grid interference such as factories with many high‑power equipment and power plants.