ABB UFC760BE43 3BHE004573R0043
Product Name
UFC760BE43 3BHE004573R0043
Product Introduction
AC 800M single-slot controller CPU module for ABB System 800xA distributed control system. Executes real-time control logic, PID loops, discrete interlock logic and local I/O data processing for compact control racks and auxiliary process units.
Detailed content
Technical Specifications
- Order Code: 3BHE004573R0043
- Controller Type: Basic single-Ethernet CPU module
- Compatible Platform: ABB System 800xA AC 800M rack
- Backplane Bus: S800 I/O rack backplane
- Supply Voltage: 24 V DC ±20% via rack backplane
- Typical Current Draw: 400 mA
- Ethernet Port: 1 × 10/100 Mbps RJ45 plant communication
- Service Port: 1 × isolated RS232
- Redundancy: Non-redundant single network variant
- PCB Protection: G3 conformal coating
- Hot Swap: System 800xA certified hot-swappable
- Operating Temperature: -20°C to +60°C
- Storage Temperature: -40°C to +85°C
- Humidity: 5% to 95% non-condensing
- Dimensions: 130 mm × 70 mm × 125 mm
- Weight: 0.44 kg
- Certifications: UL, CE, RoHS, EN61000 Class A EMC
Functional Features
- Real-time PID and discrete control execution
- Local I/O data processing through backplane bus
- Single Ethernet plant network communication
- RS232 local commissioning and configuration
- Continuous RAM/ROM self-test
- Ethernet link loss alarm
- Backplane undervoltage monitoring
- Hardware watchdog automatic recovery
- Reverse polarity protection on backplane power
Application Scenarios
- Compact skid control
- Auxiliary boiler control
- Small turbine control
- Generator auxiliary systems
- Process automation cabinets
- Non-critical auxiliary control loops
Structural Characteristics
- Single-width rack slot design
- Metal card housing
- Edge connector with gold-plated contacts
- Front-facing service port
- DIN-rail compatible rack mounting
Working Principle
The module receives process I/O data from S800 I/O through the rack backplane, executes control programs downloaded by Control Builder M, and exchanges supervisory data with the plant network through the Ethernet port.
Installation Requirements
- Install only in compatible AC 800M rack
- Confirm 24 V DC backplane power is stable
- Ensure proper grounding of control cabinet
- Keep adequate ventilation space around the module
- Verify firmware compatibility before insertion
Usage Notes
- Do not insert or remove under uncontrolled power state
- Use ESD protection during handling
- Confirm Ethernet addressing before commissioning
- Check conformal coating and connector pins before installation